Hitachi Energy Relion SAM600-IO Firmware 2.2.1
Approved changes feed: RSS · Atom
cpe:2.3:o:hitachienergy:relion_sam600-io_firmware:2.2.1:*:*:*:*:*:*:*
part: o version: 2.2.1 update: *
| Vendor | Hitachienergy (2cd248c7-aee9-59a5-80aa-6fb18cc538ff) |
|---|---|
| Product | Relion Sam600 Io Firmware (805342e9-ad7c-5c2f-bb5d-9141be4efae1) |
| Edition | * |
| Language | * |
| Software edition | * |
| Target software | * |
| Target hardware | * |
| Other | * |
| Notes | Imported from NVD CPE 2.0 feed |
PURL mappings
| PURL | Source | Last updated |
|---|---|---|
| No PURL mappings for this CPE yet. | ||
Vulnerability references
| Identifier | cpeApplicability | Submitted | db.gcve.eu details | Rationale |
|---|---|---|---|---|
CVE:CVE-2023-4518 |
vulnerable | 2026-06-03 14:53:28.403654 |
Details available
MEDIUM (6.5)
A vulnerability exists in the input validation of the GOOSE
messages where out of range values received and processed
by the IED caused a reboot of the device. In order for an
attacker to exploit the vulnerability, goose receiving blocks need
to be configured.
Published: 2023-12-01T14:18:47.387Z
Updated: 2024-09-23T12:21:46.914Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2022-3864 |
vulnerable | 2026-06-03 14:47:59.431381 |
Details available
MEDIUM (4.5)
A vulnerability exists in the Relion update package signature validation. A tampered update package could cause the IED to restart. After restart the device is back to normal operation.
An attacker could exploit the vulnerability by first gaining access to
the system with security privileges and attempt to update the IED
with a malicious update package. Successful exploitation of this
vulnerability will cause the IED to restart, causing a temporary Denial of Service.
Published: 2024-01-04T09:31:20.283Z
Updated: 2024-08-27T15:19:54.336Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2022-3353 |
vulnerable | 2026-06-03 14:47:58.159623 |
IEC 61850 MMS-Server Vulnerability in multiple Hitachi Energy Products
MEDIUM (5.9)
A vulnerability exists in the IEC 61850 communication stack that affects multiple Hitachi Energy products.
An attacker could exploit the vulnerability by using a specially crafted message sequence, to force the IEC 61850 MMS-server communication stack, to stop accepting new MMS-client connections.
Already existing/established client-server connections are not affected.
List of affected CPEs:
* cpe:2.3:o:hitachienergy:fox61x_tego1:r15b08:*:*:*:*:*:*:*
* cpe:2.3:o:hitachienergy:fox61x_tego1:r2a16_3:*:*:*:*:*:*:*
* cpe:2.3:o:hitachienergy:fox61x_tego1:r2a16:*:*:*:*:*:*:*
* cpe:2.3:o:hitachienergy:fox61x_tego1:r1e01:*:*:*:*:*:*:*
* cpe:2.3:o:hitachienergy:fox61x_tego1:r1d02:*:*:*:*:*:*:*
* cpe:2.3:o:hitachienergy:fox61x_tego1:r1c07:*:*:*:*:*:*:*
* cpe:2.3:o:hitachienergy:fox61x_tego1:r1b02:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:gms600:1.3.0:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.1.*:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.5.*:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.6.0:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.6.0.1:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.7.0:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.7.2:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.8.0:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:itt600_sa_explorer:2.0.*:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:itt600_sa_explorer:2.1.0.4:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:itt600_sa_explorer:2.1.0.5:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.*:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.4:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.4.1:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:mms:2.2.3:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:pwc600:1.0:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:pwc600:1.1:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:pwc600:1.2:*:*:*:*:*:*:*
* cpe:2.3:o:hitachienergy:reb500:7:*:*:*:*:*:*:*:*
* cpe:2.3:o:hitachienergy:reb500:8:*:*:*:*:*:*:*
* cpe:2.3:o:hitachienergy:relion670:1.2.*:*:*:*:*:*:*:*
* cpe:2.3:o:hitachienergy:relion670:2.0.*:*:*:*:*:*:*:*
* cpe:2.3:o:hitachienergy:relion650:1.1.*:*:*:*:*:*:*:*
* cpe:2.3:o:hitachienergy:relion650:1.3.*:*:*:*:*:*:*:*
* cpe:2.3:o:hitachienergy:relion650:2.1.*:*:*:*:*:*:*:*
* cpe:2.3:o:hitachienergy:relion670:2.1.*:*:*:*:*:*:*:*
* cpe:2.3:o:hitachienergy:relionSAM600-IO:2.2.1:*:*:*:*:*:*:*
* cpe:2.3:o:hitachienergy:relionSAM600-IO:2.2.5:*:*:*:*:*:*:*
* cpe:2.3:o:hitachienergy:relion670:2.2.*:*:*:*:*:*:*:*
* cpe:2.3:o:hitachienergy:relion650:2.2.*:*:*:*:*:*:*:*
* cpe:2.3:o:hitachienergy:rtu500cmu:12.*.*:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:rtu500cmu:13.*.*:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:txpert_hub_coretec_4:2.*:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:txpert_hub_coretec_4:3.0:*:*:*:*:*:*:*
* cpe:2.3:a:hitachienergy:txpert_hub_coretec_5:3.0:*:*:*:*:*:*:*
Published: 2023-02-21T13:50:46.145Z
Updated: 2025-03-12T15:17:11.275Z Reference links
|
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2021-35535 |
vulnerable | 2026-06-03 14:44:56.640677 |
Insufficient Security Control Vulnerability
HIGH (8.1)
Insecure Boot Image vulnerability in Hitachi Energy Relion Relion 670/650/SAM600-IO series allows an attacker who manages to get access to the front network port and to cause a reboot sequences of the device may exploit the vulnerability, where there is a tiny time gap during the booting process where an older version of VxWorks is loaded prior to application firmware booting, could exploit the vulnerability in the older version of VxWorks and cause a denial-of-service on the product. This issue affects: Hitachi Energy Relion 670 Series 2.2.2 all revisions; 2.2.3 versions prior to 2.2.3.3. Hitachi Energy Relion 670/650 Series 2.2.0 all revisions; 2.2.4 all revisions. Hitachi Energy Relion 670/650/SAM600-IO 2.2.1 all revisions.
Published: 2021-11-18T15:53:12.711Z
Updated: 2024-09-16T17:42:37.566Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2021-35534 |
vulnerable | 2026-06-03 14:44:56.635267 |
Insufficient Security Control Vulnerability
HIGH (7.2)
Insufficient security control vulnerability in internal database access mechanism of Hitachi Energy Relion 670/650/SAM600-IO, Relion 650, GMS600, PWC600 allows attacker who successfully exploited this vulnerability, of which the product does not sufficiently restrict access to an internal database tables, could allow anybody with user credentials to bypass security controls that is enforced by the product. Consequently, exploitation may lead to unauthorized modifications on data/firmware, and/or to permanently disabling the product. This issue affects: Hitachi Energy Relion 670 Series 2.0 all revisions; 2.2.2 all revisions; 2.2.3 versions prior to 2.2.3.5. Hitachi Energy Relion 670/650 Series 2.1 all revisions. 2.2.0 all revisions; 2.2.4 all revisions; Hitachi Energy Relion 670/650/SAM600-IO 2.2.1 all revisions; 2.2.5 versions prior to 2.2.5.2. Hitachi Energy Relion 650 1.0 all revisions. 1.1 all revisions; 1.2 all revisions; 1.3 versions prior to 1.3.0.8; Hitachi Energy GMS600 1.3.0; 1.3.0.1; 1.2.0. Hitachi Energy PWC600 1.0.1 version 1.0.1.4 and prior versions; 1.1.0 version 1.1.0.1 and prior versions.
Published: 2021-11-18T16:35:03.214Z
Updated: 2024-09-16T18:45:19.607Z Reference links
|
Imported from gcve-enriched-dumps CVE data |
Contribute