Hitachi Energy RTU500 Firmware 12.4
Approved changes feed: RSS · Atom
cpe:2.3:o:hitachienergy:rtu500_firmware:12.4:*:*:*:*:*:*:*
part: o version: 12.4 update: *
| Vendor | Hitachienergy (2cd248c7-aee9-59a5-80aa-6fb18cc538ff) |
|---|---|
| Product | Rtu500 Firmware (40405c3b-1dd0-5e2a-8fc4-969f22801fc2) |
| Edition | * |
| Language | * |
| Software edition | * |
| Target software | * |
| Target hardware | * |
| Other | * |
| Notes | Imported from NVD CPE 2.0 feed |
PURL mappings
| PURL | Source | Last updated |
|---|---|---|
| No PURL mappings for this CPE yet. | ||
Vulnerability references
| Identifier | cpeApplicability | Submitted | db.gcve.eu details | Rationale |
|---|---|---|---|---|
CVE:CVE-2021-35533 |
vulnerable | 2026-06-03 14:44:56.615640 |
Specially Crafted IEC 60870-5-104 Packet Vulnerability in RTU500 series
HIGH (7.5)
Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).
Published: 2021-11-26T16:37:27.683Z
Updated: 2024-09-16T21:02:16.277Z |
Imported from gcve-enriched-dumps CVE data |
Contribute