Approved changes feed: RSS · Atom

cpe:2.3:h:hitachienergy:rtu530:-:*:*:*:*:*:*:*

part: h version: - update: *

VendorHitachienergy (2cd248c7-aee9-59a5-80aa-6fb18cc538ff)
ProductRtu530 (e3858d9c-f74a-59e4-b2f9-534c096bd6bb)
Edition*
Language*
Software edition*
Target software*
Target hardware*
Other*
NotesImported from NVD CPE 2.0 feed

PURL mappings

PURLSourceLast updated
No PURL mappings for this CPE yet.

Vulnerability references

IdentifiercpeApplicabilitySubmitteddb.gcve.eu detailsRationale
CVE:CVE-2026-1773 not_vulnerable 2026-06-03 15:14:45.296534 Details available
IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame. Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation.
Published: 2026-02-24T13:13:17.990Z
Updated: 2026-05-27T14:50:01.447Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2026-1772 not_vulnerable 2026-06-03 15:14:45.288579 Details available
RTU500 web interface: An unprivileged user can read user management information. The information cannot be accessed via the RTU500 web user interface but requires further tools like browser development utilities to access them without required privileges.
Published: 2026-02-24T13:03:23.592Z
Updated: 2026-02-28T02:19:01.092Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-5769 not_vulnerable 2026-06-03 14:53:49.589775 Details available
MEDIUM (5.4)
A vulnerability exists in the webserver that affects the RTU500 series product versions listed below. A malicious actor could perform cross-site scripting on the webserver due to user input being improperly sanitized.
Published: 2023-12-14T16:19:51.846Z
Updated: 2024-08-02T08:07:32.850Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-5768 not_vulnerable 2026-06-03 14:53:49.589043 Details available
MEDIUM (5.9)
A vulnerability exists in the HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Incomplete or wrong received APDU frame layout may cause blocking on link layer. Error reason was an endless blocking when reading incoming frames on link layer with wrong length information of APDU or delayed reception of data octets. Only communication link of affected HCI IEC 60870-5-104 is blocked. If attack sequence stops the communication to the previously attacked link gets normal again.
Published: 2023-12-04T14:33:47.898Z
Updated: 2024-08-02T08:07:32.849Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-5767 not_vulnerable 2026-06-03 14:53:49.585302 Details available
MEDIUM (6)
A vulnerability exists in the webserver that affects the RTU500 series product versions listed below. A malicious actor could perform cross-site scripting on the webserver due to an RDT language file being improperly sanitized.
Published: 2023-12-04T14:30:23.253Z
Updated: 2024-08-02T08:07:32.705Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2022-2081 not_vulnerable 2026-06-03 14:47:00.207631 Details available
HIGH (7.5)
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is enabled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500 in a high rate, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a lack of flood control which eventually if exploited causes an internal stack overflow in the HCI Modbus TCP function.
Published: 2024-01-04T09:15:30.332Z
Updated: 2025-05-22T18:20:49.318Z
Reference links
Imported from gcve-enriched-dumps CVE data

Contribute

You can submit an edit proposal for this CPE entry or suggest a related product/vendor addition using the action button above.