Siemens SIMATIC WinCC Runtime Professional 19
Approved changes feed: RSS · Atom
cpe:2.3:a:siemens:simatic_wincc_runtime_professional:19:*:*:*:*:*:*:*
part: a version: 19 update: *
| Vendor | Siemens (4bd2a91b-02ad-5c3d-b25f-70697e0c9d7f) |
|---|---|
| Product | Simatic Wincc Runtime Professional (0863a102-eb19-5ec8-ade3-bb616f292d6f) |
| Edition | * |
| Language | * |
| Software edition | * |
| Target software | * |
| Target hardware | * |
| Other | * |
| Notes | Imported from NVD CPE 2.0 feed |
PURL mappings
| PURL | Source | Last updated |
|---|---|---|
| No PURL mappings for this CPE yet. | ||
Vulnerability references
| Identifier | cpeApplicability | Submitted | db.gcve.eu details | Rationale |
|---|---|---|---|---|
CVE:CVE-2024-35783 |
vulnerable | 2026-06-08 06:39:42.736602 |
Details available
CRITICAL (9.1)
A vulnerability has been identified in SIMATIC BATCH V9.1 (All versions), SIMATIC Information Server 2020 (All versions < V2020 SP2 Update 5), SIMATIC Information Server 2022 (All versions < V2022 SP1 Update 2), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP2 UC06), SIMATIC Process Historian 2020 (All versions < V2020 SP2 Update 5), SIMATIC Process Historian 2022 (All versions < V2022 SP1 Update 2), SIMATIC WinCC Runtime Professional V18 (All versions < V18 Update 5), SIMATIC WinCC Runtime Professional V19 (All versions < V19 Update 3), SIMATIC WinCC V7.4 (All versions), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 18), SIMATIC WinCC V8.0 (All versions < V8.0 Update 5). The affected products run their DB server with elevated privileges which could allow an authenticated attacker to execute arbitrary OS commands with administrative privileges.
Published: 2024-09-10T09:36:32.225Z
Updated: 2025-01-14T10:30:01.253Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-48364 |
vulnerable | 2026-06-08 06:14:27.037393 |
Details available
MEDIUM (6.5)
A vulnerability has been identified in OpenPCS 7 V9.1 (All versions < V9.1 SP2 UC05), SIMATIC BATCH V9.1 (All versions < V9.1 SP2 UC05), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP2 UC05), SIMATIC Route Control V9.1 (All versions < V9.1 SP2 UC05), SIMATIC WinCC Runtime Professional V18 (All versions < V18 Update 4), SIMATIC WinCC Runtime Professional V19 (All versions < V19 Update 2), SIMATIC WinCC V7.4 (All versions), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 15), SIMATIC WinCC V8.0 (All versions < V8.0 Update 4). The implementation of the RPC (Remote Procedure call) communication protocol in the affected products do not properly handle certain malformed RPC messages. An attacker could use this vulnerability to cause a denial of service condition in the RPC server.
Published: 2024-02-13T08:59:56.648Z
Updated: 2024-09-10T09:36:24.190Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-48363 |
vulnerable | 2026-06-08 06:14:27.035127 |
Details available
MEDIUM (6.5)
A vulnerability has been identified in OpenPCS 7 V9.1 (All versions < V9.1 SP2 UC05), SIMATIC BATCH V9.1 (All versions < V9.1 SP2 UC05), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP2 UC05), SIMATIC Route Control V9.1 (All versions < V9.1 SP2 UC05), SIMATIC WinCC Runtime Professional V18 (All versions < V18 Update 4), SIMATIC WinCC Runtime Professional V19 (All versions < V19 Update 2), SIMATIC WinCC V7.4 (All versions), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 15), SIMATIC WinCC V8.0 (All versions < V8.0 Update 4). The implementation of the RPC (Remote Procedure call)
communication protocol in the affected products do not
properly handle certain unorganized RPC messages. An
attacker could use this vulnerability to cause a denial of service
condition in the RPC server.
Published: 2024-02-13T08:59:55.432Z
Updated: 2024-09-10T09:36:22.958Z Reference links |
Imported from gcve-enriched-dumps CVE data |
Contribute