Simatic Step 7 (Tia Portal)
Approved changes feed: RSS · Atom
cpe:2.3:a:siemens:simatic_step_7_\(tia_portal\):*:*:*:*:*:*:*:*
part: a version: * update: *
| Vendor | Siemens (4bd2a91b-02ad-5c3d-b25f-70697e0c9d7f) |
|---|---|
| Product | Simatic Step 7 (Tia Portal) (f0a3ef21-700a-5ac6-a4cd-466c72c622e7) |
| Edition | * |
| Language | * |
| Software edition | * |
| Target software | * |
| Target hardware | * |
| Other | * |
| Notes | Imported from gcve-enriched-dumps CVE data |
PURL mappings
| PURL | Source | Last updated |
|---|---|---|
| No PURL mappings for this CPE yet. | ||
Vulnerability references
| Identifier | cpeApplicability | Submitted | db.gcve.eu details | Rationale |
|---|---|---|---|---|
CVE:CVE-2021-37172 |
vulnerable | 2026-06-08 05:32:53.475031 |
Details available
A vulnerability has been identified in SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (V4.5.0). Affected devices fail to authenticate against configured passwords when provisioned using TIA Portal V13. This could allow an attacker using TIA Portal V13 or later versions to bypass authentication and download arbitrary programs to the PLC. The vulnerability does not occur when TIA Portal V13 SP1 or any later version was used to provision the device.
Published: 2021-08-10T10:35:34.000Z
Updated: 2024-08-04T01:16:03.220Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2018-13811 |
vulnerable | 2026-06-08 05:10:51.961934 |
Details available
A vulnerability has been identified in SIMATIC STEP 7 (TIA Portal) (All Versions < V15.1). Password hashes with insufficient computational effort could allow an attacker to access to a project file and reconstruct passwords. The vulnerability could be exploited by an attacker with local access to the project file. No user interaction is required to exploit the vulnerability. The vulnerability could allow the attacker to obtain certain passwords from the project. At the time of advisory publication no public exploitation of this vulnerability was known.
Published: 2018-12-13T16:00:00.000Z
Updated: 2024-08-05T09:14:47.273Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2016-7165 |
vulnerable | 2026-06-08 05:08:12.007171 |
Details available
A vulnerability has been identified in Primary Setup Tool (PST) (All versions < V4.2 HF1), SIMATIC IT Production Suite (All versions < V7.0 SP1 HFX 2), SIMATIC NET PC-Software (All versions < V14), SIMATIC PCS 7 V7.1 (All versions), SIMATIC PCS 7 V8.0 (All versions), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1), SIMATIC STEP 7 (TIA Portal) V13 (All versions < V13 SP2), SIMATIC STEP 7 V5.X (All versions < V5.5 SP4 HF11), SIMATIC WinCC (TIA Portal) Basic, Comfort, Advanced (All versions < V14), SIMATIC WinCC (TIA Portal) Professional V13 (All versions < V13 SP2), SIMATIC WinCC (TIA Portal) Professional V14 (All versions < V14 SP1), SIMATIC WinCC Runtime Professional V13 (All versions < V13 SP2), SIMATIC WinCC Runtime Professional V14 (All versions < V14 SP1), SIMATIC WinCC V7.0 SP2 and earlier versions (All versions < V7.0 SP2 Upd 12), SIMATIC WinCC V7.0 SP3 (All versions < V7.0 SP3 Upd 8), SIMATIC WinCC V7.2 (All versions < V7.2 Upd 14), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 11), SIMATIC WinCC V7.4 (All versions < V7.4 SP1), SIMIT V9.0 (All versions < V9.0 SP1), SINEMA Remote Connect Client (All versions < V1.0 SP3), SINEMA Server (All versions < V13 SP2), SOFTNET Security Client V5.0 (All versions), Security Configuration Tool (SCT) (All versions < V4.3 HF1), TeleControl Server Basic (All versions < V3.0 SP2), WinAC RTX 2010 SP2 (All versions), WinAC RTX F 2010 SP2 (All versions). Unquoted service paths could allow local Microsoft Windows operating system users to escalate their privileges if the affected products are not installed under their default path ("C:\Program Files\*" or the localized equivalent).
Published: 2016-11-15T19:00:00.000Z
Updated: 2024-08-06T01:50:47.526Z |
Imported from gcve-enriched-dumps CVE data |
Contribute
You can submit an edit proposal for this CPE entry or suggest a related product/vendor addition using the action button above.