Approved changes feed: RSS · Atom

cpe:2.3:o:hitachienergy:relion_670_firmware:*:*:*:*:*:*:*:*

part: o version: * update: *

VendorHitachienergy (2cd248c7-aee9-59a5-80aa-6fb18cc538ff)
ProductRelion 670 Firmware (14a68f18-4849-5870-955c-63dd0cecf417)
Edition*
Language*
Software edition*
Target software*
Target hardware*
Other*
NotesImported from gcve-enriched-dumps CVE data

PURL mappings

PURLSourceLast updated
No PURL mappings for this CPE yet.

Vulnerability references

IdentifiercpeApplicabilitySubmitteddb.gcve.eu detailsRationale
CVE:CVE-2023-4518 vulnerable 2026-06-08 06:16:12.870298 Details available
MEDIUM (6.5)
A vulnerability exists in the input validation of the GOOSE messages where out of range values received and processed by the IED caused a reboot of the device. In order for an attacker to exploit the vulnerability, goose receiving blocks need to be configured.
Published: 2023-12-01T14:18:47.387Z
Updated: 2024-09-23T12:21:46.914Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2021-35535 vulnerable 2026-06-08 05:32:49.052528 Insufficient Security Control Vulnerability
HIGH (8.1)
Insecure Boot Image vulnerability in Hitachi Energy Relion Relion 670/650/SAM600-IO series allows an attacker who manages to get access to the front network port and to cause a reboot sequences of the device may exploit the vulnerability, where there is a tiny time gap during the booting process where an older version of VxWorks is loaded prior to application firmware booting, could exploit the vulnerability in the older version of VxWorks and cause a denial-of-service on the product. This issue affects: Hitachi Energy Relion 670 Series 2.2.2 all revisions; 2.2.3 versions prior to 2.2.3.3. Hitachi Energy Relion 670/650 Series 2.2.0 all revisions; 2.2.4 all revisions. Hitachi Energy Relion 670/650/SAM600-IO 2.2.1 all revisions.
Published: 2021-11-18T15:53:12.711Z
Updated: 2024-09-16T17:42:37.566Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2021-35534 vulnerable 2026-06-08 05:32:49.032078 Insufficient Security Control Vulnerability
HIGH (7.2)
Insufficient security control vulnerability in internal database access mechanism of Hitachi Energy Relion 670/650/SAM600-IO, Relion 650, GMS600, PWC600 allows attacker who successfully exploited this vulnerability, of which the product does not sufficiently restrict access to an internal database tables, could allow anybody with user credentials to bypass security controls that is enforced by the product. Consequently, exploitation may lead to unauthorized modifications on data/firmware, and/or to permanently disabling the product. This issue affects: Hitachi Energy Relion 670 Series 2.0 all revisions; 2.2.2 all revisions; 2.2.3 versions prior to 2.2.3.5. Hitachi Energy Relion 670/650 Series 2.1 all revisions. 2.2.0 all revisions; 2.2.4 all revisions; Hitachi Energy Relion 670/650/SAM600-IO 2.2.1 all revisions; 2.2.5 versions prior to 2.2.5.2. Hitachi Energy Relion 650 1.0 all revisions. 1.1 all revisions; 1.2 all revisions; 1.3 versions prior to 1.3.0.8; Hitachi Energy GMS600 1.3.0; 1.3.0.1; 1.2.0. Hitachi Energy PWC600 1.0.1 version 1.0.1.4 and prior versions; 1.1.0 version 1.1.0.1 and prior versions.
Published: 2021-11-18T16:35:03.214Z
Updated: 2024-09-16T18:45:19.607Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2021-27196 vulnerable 2026-06-08 05:30:46.044838 Specially Crafted IEC 61850 Protocol Sequence Vulnerability
HIGH (7.5)
Improper Input Validation vulnerability in Hitachi ABB Power Grids Relion 670 Series, Relion 670/650 Series, Relion 670/650/SAM600-IO, Relion 650, REB500, RTU500 Series, FOX615 (TEGO1), MSM, GMS600, PWC600 allows an attacker with access to the IEC 61850 network with knowledge of how to reproduce the attack, as well as the IP addresses of the different IEC 61850 access points (of IEDs/products), to force the device to reboot, which renders the device inoperable for approximately 60 seconds. This vulnerability affects only products with IEC 61850 interfaces. This issue affects: Hitachi ABB Power Grids Relion 670 Series 1.1; 1.2.3 versions prior to 1.2.3.20; 2.0 versions prior to 2.0.0.13; 2.1; 2.2.2 versions prior to 2.2.2.3; 2.2.3 versions prior to 2.2.3.2. Hitachi ABB Power Grids Relion 670/650 Series 2.2.0 versions prior to 2.2.0.13. Hitachi ABB Power Grids Relion 670/650/SAM600-IO 2.2.1 versions prior to 2.2.1.6. Hitachi ABB Power Grids Relion 650 1.1; 1.2; 1.3 versions prior to 1.3.0.7. Hitachi ABB Power Grids REB500 7.3; 7.4; 7.5; 7.6; 8.2; 8.3. Hitachi ABB Power Grids RTU500 Series 7.x version 7.x and prior versions; 8.x version 8.x and prior versions; 9.x version 9.x and prior versions; 10.x version 10.x and prior versions; 11.x version 11.x and prior versions; 12.x version 12.x and prior versions. Hitachi ABB Power Grids FOX615 (TEGO1) R1D02 version R1D02 and prior versions. Hitachi ABB Power Grids MSM 2.1.0 versions prior to 2.1.0. Hitachi ABB Power Grids GMS600 1.3.0 version 1.3.0 and prior versions. Hitachi ABB Power Grids PWC600 1.0 versions prior to 1.0.1.4; 1.1 versions prior to 1.1.0.1.
Published: 2021-06-14T21:20:38.696Z
Updated: 2024-09-17T03:17:31.626Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2019-18253 vulnerable 2026-06-08 05:13:11.289922 Details available
An attacker could use specially crafted paths in a specific request to read or delete files from Relion 670 Series (versions 1p1r26, 1.2.3.17, 2.0.0.10, RES670 2.0.0.4, 2.1.0.1, and prior) outside the intended directory.
Published: 2019-11-27T22:05:47.000Z
Updated: 2024-08-05T01:47:14.144Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2019-18247 vulnerable 2026-06-08 05:13:11.275273 db.gcve.eu details were skipped to keep the page responsive. Imported from gcve-enriched-dumps CVE data

Contribute

You can submit an edit proposal for this CPE entry or suggest a related product/vendor addition using the action button above.