Approved changes feed: RSS · Atom

cpe:2.3:a:bosch:building_integration_system:*:*:*:*:*:*:*:*

part: a version: * update: *

VendorBosch (fd8ddba2-7d59-56e9-89d8-6fcadc94214e)
ProductBuilding Integration System (6e2cdd5b-9021-5af8-960a-8bfb9e2ed6b6)
Edition*
Language*
Software edition*
Target software*
Target hardware*
Other*
NotesImported from gcve-enriched-dumps CVE data

PURL mappings

PURLSourceLast updated
No PURL mappings for this CPE yet.

Vulnerability references

IdentifiercpeApplicabilitySubmitteddb.gcve.eu detailsRationale
CVE:CVE-2021-23859 vulnerable 2026-06-08 05:30:03.327949 Denial of Service and Authentication Bypass Vulnerability in multiple Bosch products
CRITICAL (9.1)
An unauthenticated attacker is able to send a special HTTP request, that causes a service to crash. In case of a standalone VRM or BVMS with VRM installation this crash also opens the possibility to send further unauthenticated commands to the service. On some products the interface is only local accessible lowering the CVSS base score. For a list of modified CVSS scores, please see the official Bosch Advisory Appendix chapter Modified CVSS Scores for CVE-2021-23859
Published: 2021-12-08T21:17:23.528Z
Updated: 2024-09-16T19:45:43.543Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2021-23843 vulnerable 2026-06-08 05:30:03.136560 Lack of authentication mechanisms on the device
HIGH (8.8)
The Bosch software tools AccessIPConfig.exe and AmcIpConfig.exe are used to configure certains settings in AMC2 devices. The tool allows putting a password protection on configured devices to restrict access to the configuration of an AMC2. An attacker can circumvent this protection and make unauthorized changes to configuration data on the device. An attacker can exploit this vulnerability to manipulate the device\'s configuration or make it unresponsive in the local network. The attacker needs to have access to the local network, typically even the same subnet.
Published: 2022-01-19T20:38:55.465Z
Updated: 2024-09-16T23:01:30.470Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2021-23842 vulnerable 2026-06-08 05:30:03.135893 Use of Hard-coded Cryptographic Key
MEDIUM (5.7)
Communication to the AMC2 uses a state-of-the-art cryptographic algorithm for symmetric encryption called Blowfish. An attacker could retrieve the key from the firmware to decrypt network traffic between the AMC2 and the host system. Thus, an attacker can exploit this vulnerability to decrypt and modify network traffic, decrypt and further investigate the device\'s firmware file, and change the device configuration. The attacker needs to have access to the local network, typically even the same subnet.
Published: 2022-01-19T20:38:54.368Z
Updated: 2024-09-16T21:56:51.896Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2019-6958 vulnerable 2026-06-08 05:14:13.544653 Improper Access Control for Bosch Video Systems, PSIM and Access Control Systems
CRITICAL (9.8)
A recently discovered security vulnerability affects all Bosch Video Management System (BVMS) versions 9.0 and below, DIVAR IP 2000, 3000, 5000 and 7000, Configuration Manager, Building Integration System (BIS) with Video Engine, Access Professional Edition (APE), Access Easy Controller (AEC), Bosch Video Client (BVC) and Video SDK (VSDK). The RCP+ network port allows access without authentication. Adding authentication feature to the respective library fixes the issue. The issue is classified as "CWE-284: Improper Access Control." This vulnerability, for example, allows a potential attacker to delete video or read video data.
Published: 2019-05-29T18:47:37.354Z
Updated: 2024-09-17T00:46:00.474Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2019-6957 vulnerable 2026-06-08 05:14:13.524092 Buffer Overflow for Bosch Video Systems, PSIM and Access Control Systems
CRITICAL (9.8)
A recently discovered security vulnerability affects all Bosch Video Management System (BVMS) versions 9.0 and below, DIVAR IP 2000, 3000, 5000 and 7000, Video Recording Manager (VRM), Video Streaming Gateway (VSG), Configuration Manager, Building Integration System (BIS) with Video Engine, Access Professional Edition (APE), Access Easy Controller (AEC), Bosch Video Client (BVC) and Video SDK (VSDK). The vulnerability potentially allows the unauthorized execution of code in the system via the network interface.
Published: 2019-05-29T18:55:20.387Z
Updated: 2024-09-16T16:38:39.411Z
Reference links
Imported from gcve-enriched-dumps CVE data

Contribute

You can submit an edit proposal for this CPE entry or suggest a related product/vendor addition using the action button above.