Approved changes feed: RSS · Atom

cpe:2.3:a:abb:advabuild:3.0:*:*:*:*:*:*:*

part: a version: 3.0 update: *

VendorAbb (6be1db4f-4f59-5a03-a118-0ff43377170e)
ProductAdvabuild (f54a58b3-125d-5636-922a-a28b8aa90ac4)
Edition*
Language*
Software edition*
Target software*
Target hardware*
Other*
NotesImported from gcve-enriched-dumps CVE data

PURL mappings

PURLSourceLast updated
No PURL mappings for this CPE yet.

Vulnerability references

IdentifiercpeApplicabilitySubmitteddb.gcve.eu detailsRationale
CVE:CVE-2020-11639 vulnerable 2026-06-08 05:16:47.532683 Insufficient access control on Inter process communication,
HIGH (7.8)
An attacker could exploit the vulnerability by injecting garbage data or specially crafted data. Depending on the data injected each process might be affected differently. The process could crash or cause communication issues on the affected node, effectively causing a denial-of-service attack. The attacker could tamper with the data transmitted, causing the product to store wrong information or act on wrong data or display wrong information. This issue affects Advant MOD 300 AdvaBuild: from 3.0 through 3.7 SP2. For an attack to be successful, the attacker must have local access to a node in the system and be able to start a specially crafted application that disrupts the communication. An attacker who successfully exploited the vulnerability would be able to manipulate the data in such way as allowing reads and writes to the controllers or cause Windows processes in 800xA for MOD 300 and AdvaBuild to crash.
Published: 2024-07-23T17:26:55.489Z
Updated: 2024-08-04T11:35:13.593Z
Reference links
Imported from gcve-enriched-dumps CVE data

Contribute

You can submit an edit proposal for this CPE entry or suggest a related product/vendor addition using the action button above.