Approved changes feed: RSS · Atom

cpe:2.3:a:idec:windldr:*:*:*:*:*:*:*:*

part: a version: * update: *

VendorIdec (bf6b3390-6bdb-55cd-b548-6362b8f4eefc)
ProductWindldr (00d2edd5-b2a9-55ba-8f75-b765b0284fce)
Edition*
Language*
Software edition*
Target software*
Target hardware*
Other*
NotesImported from gcve-enriched-dumps CVE data

PURL mappings

PURLSourceLast updated
No PURL mappings for this CPE yet.

Vulnerability references

IdentifiercpeApplicabilitySubmitteddb.gcve.eu detailsRationale
CVE:CVE-2024-41716 vulnerable 2026-06-08 06:43:54.959810 Details available
Cleartext storage of sensitive information vulnerability exists in WindLDR and WindO/I-NV4. If this vulnerability is exploited, an attacker who obtained the product's project file may obtain user credentials of the PLC or Operator Interfaces. As a result, an attacker may be able to manipulate and/or suspend the PLC and Operator Interfaces by accessing or hijacking them.
Published: 2024-09-04T00:34:12.610Z
Updated: 2025-03-13T14:15:40.744Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2021-37401 vulnerable 2026-06-08 05:32:54.097426 Details available
An attacker may obtain the user credentials from file servers, backup repositories, or ZLD files saved in SD cards. As a result, the PLC user program may be uploaded, altered, and/or downloaded.
Published: 2021-12-28T12:09:52.000Z
Updated: 2024-08-04T01:16:03.966Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2021-37400 vulnerable 2026-06-08 05:32:54.089538 Details available
An attacker may obtain the user credentials from the communication between the PLC and the software. As a result, the PLC user program may be uploaded, altered, and/or downloaded.
Published: 2021-12-28T12:09:59.000Z
Updated: 2024-08-04T01:16:04.056Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2021-20827 vulnerable 2026-06-08 05:29:10.598759 Details available
Plaintext storage of a password vulnerability in IDEC PLCs (FC6A Series MICROSmart All-in-One CPU module v2.32 and earlier, FC6A Series MICROSmart Plus CPU module v1.91 and earlier, WindLDR v8.19.1 and earlier, WindEDIT Lite v1.3.1 and earlier, and Data File Manager v2.12.1 and earlier) allows an attacker to obtain the PLC Web server user credentials from file servers, backup repositories, or ZLD files saved in SD cards. As a result, the attacker may access the PLC Web server and hijack the PLC, and manipulation of the PLC output and/or suspension of the PLC may be conducted.
Published: 2021-12-24T06:30:27.000Z
Updated: 2024-08-03T17:53:22.806Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2021-20826 vulnerable 2026-06-08 05:29:10.598147 Details available
Unprotected transport of credentials vulnerability in IDEC PLCs (FC6A Series MICROSmart All-in-One CPU module v2.32 and earlier, FC6A Series MICROSmart Plus CPU module v1.91 and earlier, WindLDR v8.19.1 and earlier, WindEDIT Lite v1.3.1 and earlier, and Data File Manager v2.12.1 and earlier) allows an attacker to obtain the PLC Web server user credentials from the communication between the PLC and the software. As a result, the complete access privileges to the PLC Web server may be obtained, and manipulation of the PLC output and/or suspension of the PLC may be conducted.
Published: 2021-12-24T06:30:26.000Z
Updated: 2024-08-03T17:53:22.508Z
Reference links
Imported from gcve-enriched-dumps CVE data

Contribute