Approved changes feed: RSS · Atom

cpe:2.3:a:hitachi_energy:rtu500_series_cmu_firmware:*:*:*:*:*:*:*:*

part: a version: * update: *

VendorHitachi Energy (57ae0a6c-1cbf-5100-9bbb-0f210f6013d6)
ProductRtu500 Series Cmu Firmware (f1efc59d-1f75-5282-b288-15912d33c6aa)
Edition*
Language*
Software edition*
Target software*
Target hardware*
Other*
NotesImported from gcve-enriched-dumps CVE data

PURL mappings

PURLSourceLast updated
No PURL mappings for this CPE yet.

Vulnerability references

IdentifiercpeApplicabilitySubmitteddb.gcve.eu detailsRationale
CVE:CVE-2026-8479 vulnerable 2026-06-08 08:08:58.387926 Details available
IEC 60870-5-104 used in bidirectional mode in RTU500 is vulnerable for a NULL pointer dereferencing, if a specially crafted sequence of messages is sent for a certain time, causing Denial of Service impact. Product is only affected if IEC 60870-5-104 functionality in bidirectional mode (BCI) is configured.
Published: 2026-05-26T11:54:09.962Z
Updated: 2026-05-26T14:49:40.036Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2026-1773 vulnerable 2026-06-08 07:49:09.584219 Details available
IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame. Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation.
Published: 2026-02-24T13:13:17.990Z
Updated: 2026-05-27T14:50:01.447Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2026-1772 vulnerable 2026-06-08 07:49:09.570704 Details available
RTU500 web interface: An unprivileged user can read user management information. The information cannot be accessed via the RTU500 web user interface but requires further tools like browser development utilities to access them without required privileges.
Published: 2026-02-24T13:03:23.592Z
Updated: 2026-02-28T02:19:01.092Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2024-2617 vulnerable 2026-06-08 06:33:31.652631 Details available
HIGH (7.2)
A vulnerability exists in the RTU500 that allows for authenticated and authorized users to bypass secure update, if secure update feature was not enabled on all CMUs of a RTU500. If a malicious actor successfully exploits this vulnerability, they could use it to update the RTU500 with unsigned firmware.
Published: 2024-04-30T12:57:37.143Z
Updated: 2026-03-04T12:02:50.897Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2024-1532 vulnerable 2026-06-08 06:27:13.280707 Details available
MEDIUM (6.8)
A vulnerability exists in the stb-language file handling that affects the RTU500 series product versions listed below. A malicious actor could enforce diagnostic texts being displayed as empty strings, if an authorized user uploads a specially crafted stb-language file.
Published: 2024-03-27T01:52:15.671Z
Updated: 2024-08-01T19:22:34.888Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2024-1531 vulnerable 2026-06-08 06:27:13.280146 db.gcve.eu details were skipped to keep the page responsive. Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-6711 vulnerable 2026-06-08 06:21:55.354978 db.gcve.eu details were skipped to keep the page responsive. Imported from gcve-enriched-dumps CVE data
CVE:CVE-2022-2081 vulnerable 2026-06-08 05:42:50.222538 db.gcve.eu details were skipped to keep the page responsive. Imported from gcve-enriched-dumps CVE data
CVE:CVE-2022-28613 vulnerable 2026-06-08 05:42:44.645382 db.gcve.eu details were skipped to keep the page responsive. Imported from gcve-enriched-dumps CVE data