Approved changes feed: RSS · Atom

cpe:2.3:a:hitachi_energy:rtu500_series_cmu_firmware:*:*:*:*:*:*:*:*

part: a version: * update: *

VendorHitachi Energy (57ae0a6c-1cbf-5100-9bbb-0f210f6013d6)
ProductRtu500 Series Cmu Firmware (f1efc59d-1f75-5282-b288-15912d33c6aa)
Edition*
Language*
Software edition*
Target software*
Target hardware*
Other*
NotesImported from gcve-enriched-dumps CVE data

PURL mappings

PURLSourceLast updated
No PURL mappings for this CPE yet.

Vulnerability references

IdentifiercpeApplicabilitySubmitteddb.gcve.eu detailsRationale
CVE:CVE-2026-8479 vulnerable 2026-06-03 15:27:57.967442 Details available
IEC 60870-5-104 used in bidirectional mode in RTU500 is vulnerable for a NULL pointer dereferencing, if a specially crafted sequence of messages is sent for a certain time, causing Denial of Service impact. Product is only affected if IEC 60870-5-104 functionality in bidirectional mode (BCI) is configured.
Published: 2026-05-26T11:54:09.962Z
Updated: 2026-05-26T14:49:40.036Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2026-1773 vulnerable 2026-06-03 15:14:45.293321 Details available
IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame. Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation.
Published: 2026-02-24T13:13:17.990Z
Updated: 2026-05-27T14:50:01.447Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2026-1772 vulnerable 2026-06-03 15:14:45.283091 Details available
RTU500 web interface: An unprivileged user can read user management information. The information cannot be accessed via the RTU500 web user interface but requires further tools like browser development utilities to access them without required privileges.
Published: 2026-02-24T13:03:23.592Z
Updated: 2026-02-28T02:19:01.092Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2024-2617 vulnerable 2026-06-03 14:55:29.748626 Details available
HIGH (7.2)
A vulnerability exists in the RTU500 that allows for authenticated and authorized users to bypass secure update, if secure update feature was not enabled on all CMUs of a RTU500. If a malicious actor successfully exploits this vulnerability, they could use it to update the RTU500 with unsigned firmware.
Published: 2024-04-30T12:57:37.143Z
Updated: 2026-03-04T12:02:50.897Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2024-1532 vulnerable 2026-06-03 14:54:27.217672 Details available
MEDIUM (6.8)
A vulnerability exists in the stb-language file handling that affects the RTU500 series product versions listed below. A malicious actor could enforce diagnostic texts being displayed as empty strings, if an authorized user uploads a specially crafted stb-language file.
Published: 2024-03-27T01:52:15.671Z
Updated: 2024-08-01T19:22:34.888Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2024-1531 vulnerable 2026-06-03 14:54:27.217232 Details available
HIGH (8.2)
A vulnerability exists in the stb-language file handling that affects the RTU500 series product versions listed below. A malicious actor could print random memory content in the RTU500 system log, if an authorized user uploads a specially crafted stb-language file.
Published: 2024-03-27T01:45:44.463Z
Updated: 2024-08-05T15:50:58.451Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-6711 vulnerable 2026-06-03 14:53:58.728775 Details available
MEDIUM (5.9)
Vulnerability exists in SCI IEC 60870-5-104 and HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Specially crafted messages sent to the mentioned components are not validated properly and can result in buffer overflow and as final consequence to a reboot of an RTU500 CMU.
Published: 2023-12-19T14:53:44.658Z
Updated: 2024-09-25T08:43:52.208Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2022-2081 vulnerable 2026-06-03 14:47:00.201847 Details available
HIGH (7.5)
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is enabled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500 in a high rate, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a lack of flood control which eventually if exploited causes an internal stack overflow in the HCI Modbus TCP function.
Published: 2024-01-04T09:15:30.332Z
Updated: 2025-05-22T18:20:49.318Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2022-28613 vulnerable 2026-06-03 14:46:54.940840 Specially Crafted Modbus TCP Packet Vulnerability in RTU500 series
HIGH (7.5)
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function.
Published: 2022-05-02T19:01:06.262Z
Updated: 2024-09-25T07:58:13.187Z
Reference links
Imported from gcve-enriched-dumps CVE data

Contribute

You can submit an edit proposal for this CPE entry or suggest a related product/vendor addition using the action button above.