Rtu500 Series Cmu Firmware
Approved changes feed: RSS · Atom
cpe:2.3:a:hitachi_energy:rtu500_series_cmu_firmware:*:*:*:*:*:*:*:*
part: a version: * update: *
| Vendor | Hitachi Energy (57ae0a6c-1cbf-5100-9bbb-0f210f6013d6) |
|---|---|
| Product | Rtu500 Series Cmu Firmware (f1efc59d-1f75-5282-b288-15912d33c6aa) |
| Edition | * |
| Language | * |
| Software edition | * |
| Target software | * |
| Target hardware | * |
| Other | * |
| Notes | Imported from gcve-enriched-dumps CVE data |
PURL mappings
| PURL | Source | Last updated |
|---|---|---|
| No PURL mappings for this CPE yet. | ||
Vulnerability references
| Identifier | cpeApplicability | Submitted | db.gcve.eu details | Rationale |
|---|---|---|---|---|
CVE:CVE-2026-8479 |
vulnerable | 2026-06-08 08:08:58.387926 |
Details available
IEC 60870-5-104 used in bidirectional mode in RTU500 is vulnerable
for a NULL pointer dereferencing, if a specially crafted
sequence of messages is sent for a certain time, causing
Denial of Service impact.
Product is only affected if IEC 60870-5-104 functionality in
bidirectional mode (BCI) is configured.
Published: 2026-05-26T11:54:09.962Z
Updated: 2026-05-26T14:49:40.036Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2026-1773 |
vulnerable | 2026-06-08 07:49:09.584219 |
Details available
IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame. Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation.
Published: 2026-02-24T13:13:17.990Z
Updated: 2026-05-27T14:50:01.447Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2026-1772 |
vulnerable | 2026-06-08 07:49:09.570704 |
Details available
RTU500 web interface: An unprivileged user can read user management information. The information cannot be accessed via the RTU500 web user interface but requires further tools like browser development utilities to access them without required privileges.
Published: 2026-02-24T13:03:23.592Z
Updated: 2026-02-28T02:19:01.092Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2024-2617 |
vulnerable | 2026-06-08 06:33:31.652631 |
Details available
HIGH (7.2)
A vulnerability exists in the RTU500 that allows for authenticated and authorized users to bypass secure update,
if secure update feature was not enabled on all
CMUs of a RTU500. If a
malicious actor successfully exploits this vulnerability, they
could use it to update the RTU500 with unsigned firmware.
Published: 2024-04-30T12:57:37.143Z
Updated: 2026-03-04T12:02:50.897Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2024-1532 |
vulnerable | 2026-06-08 06:27:13.280707 |
Details available
MEDIUM (6.8)
A vulnerability exists in the stb-language file handling that affects the RTU500 series product versions listed below. A malicious actor could enforce diagnostic texts being displayed as empty strings, if an authorized user uploads a specially crafted stb-language file.
Published: 2024-03-27T01:52:15.671Z
Updated: 2024-08-01T19:22:34.888Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2024-1531 |
vulnerable | 2026-06-08 06:27:13.280146 | db.gcve.eu details were skipped to keep the page responsive. | Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-6711 |
vulnerable | 2026-06-08 06:21:55.354978 | db.gcve.eu details were skipped to keep the page responsive. | Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2022-2081 |
vulnerable | 2026-06-08 05:42:50.222538 | db.gcve.eu details were skipped to keep the page responsive. | Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2022-28613 |
vulnerable | 2026-06-08 05:42:44.645382 | db.gcve.eu details were skipped to keep the page responsive. | Imported from gcve-enriched-dumps CVE data |
Contribute