Rtu540 Firmware
Approved changes feed: RSS · Atom
cpe:2.3:o:hitachienergy:rtu540_firmware:*:*:*:*:*:*:*:*
part: o version: * update: *
| Vendor | Hitachienergy (2cd248c7-aee9-59a5-80aa-6fb18cc538ff) |
|---|---|
| Product | Rtu540 Firmware (3a3cdcff-09ce-5b75-a5a7-2be57aa1a400) |
| Edition | * |
| Language | * |
| Software edition | * |
| Target software | * |
| Target hardware | * |
| Other | * |
| Notes | Imported from gcve-enriched-dumps CVE data |
PURL mappings
| PURL | Source | Last updated |
|---|---|---|
| No PURL mappings for this CPE yet. | ||
Vulnerability references
| Identifier | cpeApplicability | Submitted | db.gcve.eu details | Rationale |
|---|---|---|---|---|
CVE:CVE-2026-1773 |
vulnerable | 2026-06-03 15:14:45.293461 |
Details available
IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame. Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation.
Published: 2026-02-24T13:13:17.990Z
Updated: 2026-05-27T14:50:01.447Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2026-1772 |
vulnerable | 2026-06-03 15:14:45.289281 |
Details available
RTU500 web interface: An unprivileged user can read user management information. The information cannot be accessed via the RTU500 web user interface but requires further tools like browser development utilities to access them without required privileges.
Published: 2026-02-24T13:03:23.592Z
Updated: 2026-02-28T02:19:01.092Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-5769 |
vulnerable | 2026-06-03 14:53:49.589792 |
Details available
MEDIUM (5.4)
A vulnerability exists in the webserver that affects the
RTU500 series product versions listed below. A malicious
actor could perform cross-site scripting on the webserver
due to user input being improperly sanitized.
Published: 2023-12-14T16:19:51.846Z
Updated: 2024-08-02T08:07:32.850Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-5768 |
vulnerable | 2026-06-03 14:53:49.589061 |
Details available
MEDIUM (5.9)
A vulnerability exists in the HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below.
Incomplete or wrong received APDU frame layout may
cause blocking on link layer. Error reason was an endless blocking when reading incoming frames on link layer
with wrong length information of APDU or delayed reception
of data octets.
Only communication link of affected HCI IEC 60870-5-104
is blocked. If attack sequence stops the communication to
the previously attacked link gets normal again.
Published: 2023-12-04T14:33:47.898Z
Updated: 2024-08-02T08:07:32.849Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-5767 |
vulnerable | 2026-06-03 14:53:49.585785 |
Details available
MEDIUM (6)
A vulnerability exists in the webserver that affects the
RTU500 series product versions listed below. A malicious
actor could perform cross-site scripting on the webserver
due to an RDT language file being improperly sanitized.
Published: 2023-12-04T14:30:23.253Z
Updated: 2024-08-02T08:07:32.705Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2022-2081 |
vulnerable | 2026-06-03 14:47:00.208709 |
Details available
HIGH (7.5)
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is enabled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500 in a high rate, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a lack of flood control which eventually if exploited causes an internal stack overflow in the HCI Modbus TCP function.
Published: 2024-01-04T09:15:30.332Z
Updated: 2025-05-22T18:20:49.318Z |
Imported from gcve-enriched-dumps CVE data |
Contribute
You can submit an edit proposal for this CPE entry or suggest a related product/vendor addition using the action button above.