Micrologix 1100
Approved changes feed: RSS · Atom
cpe:2.3:a:rockwell_automation:micrologix_1100:*:*:*:*:*:*:*:*
part: a version: * update: *
| Vendor | Rockwell Automation (dde15a4c-943a-57fe-888d-2bc03ade6545) |
|---|---|
| Product | Micrologix 1100 (4cb5d80b-35b2-5b2f-aa36-d0a0c308e235) |
| Edition | * |
| Language | * |
| Software edition | * |
| Target software | * |
| Target hardware | * |
| Other | * |
| Notes | Imported from gcve-enriched-dumps CVE data |
PURL mappings
| PURL | Source | Last updated |
|---|---|---|
| No PURL mappings for this CPE yet. | ||
Vulnerability references
| Identifier | cpeApplicability | Submitted | db.gcve.eu details | Rationale |
|---|---|---|---|---|
CVE:CVE-2022-3166 |
vulnerable | 2026-06-08 05:47:19.599500 |
MicroLogix 1100 & 1400 Product Web Server Application Vulnerable to Denial-Of-Service Condition Attack
HIGH (7.5)
Rockwell Automation was made aware that the webservers of the Micrologix 1100 and 1400 controllers contain a vulnerability that may lead to a denial-of-service condition. The security vulnerability could be exploited by an attacker with network access to the affected systems by sending TCP packets to webserver and closing it abruptly which would cause a denial-of-service condition for the web server application on the device
Published: 2022-12-16T19:59:25.261Z
Updated: 2025-04-17T15:30:27.677Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2022-2179 |
vulnerable | 2026-06-08 05:42:50.397028 |
ICSA-22-188-01 Rockwell Automation MicroLogix Improper Restriction of Rendered UI Layers or Frames
MEDIUM (6.5)
The X-Frame-Options header in Rockwell Automation MicroLogix 1100/1400 Versions 21.007 and prior is not configured in the HTTP response, which could allow clickjacking attacks.
Published: 2022-07-20T15:36:33.007Z
Updated: 2025-04-16T16:14:37.655Z |
Imported from gcve-enriched-dumps CVE data |
Contribute
You can submit an edit proposal for this CPE entry or suggest a related product/vendor addition using the action button above.