Approved changes feed: RSS · Atom

cpe:2.3:o:honeywell:safety_manager_firmware:*:*:*:*:*:*:*:*

part: o version: * update: *

VendorHoneywell (98681534-528d-57d2-bf2a-17f1d63c09c9)
ProductSafety Manager Firmware (47101825-5beb-5b59-b7ba-ab5cab942fa3)
Edition*
Language*
Software edition*
Target software*
Target hardware*
Other*
NotesImported from gcve-enriched-dumps CVE data

PURL mappings

PURLSourceLast updated
No PURL mappings for this CPE yet.

Vulnerability references

IdentifiercpeApplicabilitySubmitteddb.gcve.eu detailsRationale
CVE:CVE-2022-30314 vulnerable 2026-06-08 05:43:37.934458 Details available
Honeywell Experion PKS Safety Manager 5.02 uses Hard-coded Credentials. According to FSCT-2022-0052, there is a Honeywell Experion PKS Safety Manager hardcoded credentials issue. The affected components are characterized as: POLO bootloader. The potential impact is: Manipulate firmware. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 serial interface for firmware management purposes. When booting, the Safety Manager exposes the Enea POLO bootloader via this interface. Access to the boot configuration is controlled by means of credentials hardcoded in the Safety Manager firmware. The credentials for the bootloader are hardcoded in the firmware. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize these credentials to control the boot process and manipulate the unauthenticated firmware image (see FSCT-2022-0054).
Published: 2022-07-28T15:41:20.000Z
Updated: 2024-08-03T06:48:36.171Z
Reference links
Imported from gcve-enriched-dumps CVE data

Contribute

You can submit an edit proposal for this CPE entry or suggest a related product/vendor addition using the action button above.