Infrasuite Device Master
Approved changes feed: RSS · Atom
cpe:2.3:a:deltaww:infrasuite_device_master:*:*:*:*:*:*:*:*
part: a version: * update: *
| Vendor | Deltaww (ad3e3879-744a-547a-8a68-13ba5faaf0a4) |
|---|---|
| Product | Infrasuite Device Master (eedd7529-b297-5143-9e42-d1a5d10c0cf4) |
| Edition | * |
| Language | * |
| Software edition | * |
| Target software | * |
| Target hardware | * |
| Other | * |
| Notes | Imported from gcve-enriched-dumps CVE data |
PURL mappings
| PURL | Source | Last updated |
|---|---|---|
| No PURL mappings for this CPE yet. | ||
Vulnerability references
| Identifier | cpeApplicability | Submitted | db.gcve.eu details | Rationale |
|---|---|---|---|---|
CVE:CVE-2024-10456 |
vulnerable | 2026-06-03 14:54:11.767526 |
Delta Electronics InfraSuite Device Master Deserialization of Untrusted Data
CRITICAL (9.8)
Delta Electronics InfraSuite Device Master versions prior to 1.0.12 are affected by a deserialization vulnerability that targets the Device-Gateway, which could allow deserialization of arbitrary .NET objects prior to authentication.
Published: 2024-10-30T18:04:52.786Z
Updated: 2024-10-30T18:15:45.431Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-34347 |
vulnerable | 2026-06-03 14:52:16.270798 |
Delta Electronics InfraSuite Device Master Deserialization of Untrusted Data
CRITICAL (9.8)
Delta Electronics InfraSuite Device Master versions prior to 1.0.7 contains classes that cannot be deserialized, which could allow an attack to remotely execute arbitrary code.
Published: 2023-07-10T18:59:30.158Z
Updated: 2024-11-08T17:43:56.320Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-34316 |
vulnerable | 2026-06-03 14:52:16.228683 |
Delta Electronics InfraSuite Device Master Improper Access Control
MEDIUM (6.5)
An attacker could bypass the latest Delta Electronics InfraSuite Device Master (versions prior to 1.0.7) patch, which could allow an attacker to retrieve file contents.
Published: 2023-07-10T19:01:51.280Z
Updated: 2025-01-27T16:20:03.560Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-30765 |
vulnerable | 2026-06-03 14:51:53.697006 |
Delta Electronics InfraSuite Device Master Improper Access Control
HIGH (8.8)
Delta Electronics InfraSuite Device Master versions prior to 1.0.7 contain improper access controls that could allow an attacker to alter privilege management configurations, resulting in privilege escalation.
Published: 2023-07-10T19:04:41.114Z
Updated: 2025-01-27T16:19:08.718Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-1145 |
vulnerable | 2026-06-03 14:48:53.835784 |
Details available
HIGH (7.8)
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 are affected by a deserialization vulnerability targeting the Device-DataCollect service, which could allow deserialization of requests prior to authentication, resulting in remote code execution.
Published: 2023-03-27T14:56:30.287Z
Updated: 2025-01-16T21:39:05.219Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-1144 |
vulnerable | 2026-06-03 14:48:53.835392 |
CVE-2023-1144
HIGH (8.8)
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contains an improper access control vulnerability in which an attacker can use the Device-Gateway service and bypass authorization, which could result in privilege escalation.
Published: 2023-03-27T14:43:11.987Z
Updated: 2025-01-16T21:40:57.021Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-1143 |
vulnerable | 2026-06-03 14:48:53.835096 |
CVE-2023-1143
HIGH (8.8)
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an attacker could use Lua scripts, which could allow an attacker to remotely execute arbitrary code.
Published: 2023-03-27T14:46:20.000Z
Updated: 2025-01-16T21:39:49.421Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-1142 |
vulnerable | 2026-06-03 14:48:53.834807 |
CVE-2023-1142
HIGH (7.5)
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an attacker could use URL decoding to retrieve system files, credentials, and bypass authentication resulting in privilege escalation.
Published: 2023-03-27T14:48:55.406Z
Updated: 2025-01-16T21:39:34.845Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-1141 |
vulnerable | 2026-06-03 14:48:53.834529 |
CVE-2023-1141
HIGH (8.8)
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a command injection vulnerability that could allow an attacker to inject arbitrary commands, which could result in remote code execution.
Published: 2023-03-27T14:51:43.547Z
Updated: 2025-01-16T21:39:20.180Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-1140 |
vulnerable | 2026-06-03 14:48:53.834238 |
CVE-2023-1140
CRITICAL (9.8)
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability that could allow an attacker to achieve unauthenticated remote code execution in the context of an administrator.
Published: 2023-03-27T14:54:53.192Z
Updated: 2025-01-16T21:39:13.175Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-1139 |
vulnerable | 2026-06-03 14:48:53.833949 |
CVE-2023-1139
HIGH (8.8)
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 are affected by a deserialization vulnerability targeting the Device-gateway service, which could allow deserialization of requests prior to authentication, resulting in remote code execution.
Published: 2023-03-27T14:36:28.810Z
Updated: 2025-01-16T21:41:21.901Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-1138 |
vulnerable | 2026-06-03 14:48:53.833648 |
CVE-2023-1138
HIGH (7.5)
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain an improper access control vulnerability, which could allow an attacker to retrieve Gateway configuration files to obtain plaintext credentials.
Published: 2023-03-27T14:41:48.610Z
Updated: 2025-01-16T21:41:09.760Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-1137 |
vulnerable | 2026-06-03 14:48:53.833340 |
CVE-2023-1137
MEDIUM (6.5)
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability in which a low-level user could extract files and plaintext credentials of administrator users, resulting in privilege escalation.
Published: 2023-03-27T14:44:40.332Z
Updated: 2025-01-16T21:40:39.590Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-1136 |
vulnerable | 2026-06-03 14:48:53.833027 |
CVE-2023-1136
CRITICAL (9.8)
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an unauthenticated attacker could generate a valid token, which would lead to authentication bypass.
Published: 2023-03-27T14:50:18.966Z
Updated: 2025-01-16T21:39:27.485Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-1135 |
vulnerable | 2026-06-03 14:48:53.832716 |
Details available
HIGH (7.8)
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an attacker could set incorrect directory permissions, which could result in local privilege escalation.
Published: 2023-03-27T14:59:57.462Z
Updated: 2025-01-16T21:38:57.559Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-1134 |
vulnerable | 2026-06-03 14:48:53.832284 |
CVE-2023-1134
HIGH (7.1)
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 are affected by a path traversal vulnerability, which could allow an attacker to read local files, disclose plaintext credentials, and escalate privileges.
Published: 2023-03-27T14:47:43.501Z
Updated: 2025-01-16T21:39:42.531Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-1133 |
vulnerable | 2026-06-03 14:48:53.831854 |
CVE-2023-1133
CRITICAL (9.8)
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability in which the Device-status service listens on port 10100/ UDP by default. The service accepts the unverified UDP packets and deserializes the content, which could allow an unauthenticated attacker to remotely execute arbitrary code.
Published: 2023-03-27T14:33:18.921Z
Updated: 2025-02-13T16:39:15.943Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2022-41779 |
vulnerable | 2026-06-03 14:48:05.979435 |
Details available
HIGH (8.8)
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize network packets without proper verification. If the device connects to an attacker-controlled server, the attacker could send maliciously crafted packets that would be deserialized and executed, leading to remote code execution.
Published: 2022-10-31T19:19:35.913Z
Updated: 2025-04-16T17:43:44.238Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2022-41778 |
vulnerable | 2026-06-03 14:48:05.979046 |
Details available
CRITICAL (9.8)
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize user-supplied data provided through the Device-DataCollect service port without proper verification. An attacker could provide malicious serialized objects to execute arbitrary code upon deserialization.
Published: 2023-01-12T23:19:47.452Z
Updated: 2025-01-16T22:02:07.832Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2022-41776 |
vulnerable | 2026-06-03 14:48:05.973949 |
Details available
HIGH (7.5)
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior allow unauthenticated users to trigger the WriteConfiguration method, which could allow an attacker to provide new values for user configuration files such as UserListInfo.xml. This could lead to the changing of administrative passwords.
Published: 2022-10-31T19:48:17.936Z
Updated: 2025-04-16T16:06:29.428Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2022-41772 |
vulnerable | 2026-06-03 14:48:05.972849 |
Details available
CRITICAL (9.8)
Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior mishandle .ZIP archives containing characters used in path traversal. This path traversal could result in remote code execution.
Published: 2022-10-31T19:26:33.695Z
Updated: 2025-04-16T16:06:52.076Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2022-41688 |
vulnerable | 2026-06-03 14:48:05.799656 |
Details available
CRITICAL (9.8)
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior lack proper authentication for functions that create and modify user groups. An attacker could provide malicious serialized objects that could run these functions without authentication to create a new user and add them to the administrator group.
Published: 2022-10-31T19:38:21.943Z
Updated: 2025-04-16T16:06:36.155Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2022-41657 |
vulnerable | 2026-06-03 14:48:05.712766 |
Details available
CRITICAL (9.8)
Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior allow attacker provided data already serialized into memory to be used in file operation application programmable interfaces (APIs). This could create arbitrary files, which could be used in API operations and could ultimately result in remote code execution.
Published: 2022-10-31T19:24:37.976Z
Updated: 2025-04-16T16:06:59.095Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2022-41644 |
vulnerable | 2026-06-03 14:48:05.690474 |
Details available
HIGH (8.8)
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior lacks authentication for a function that changes group privileges. An attacker could use this to create a denial-of-service state or escalate their own privileges.
Published: 2022-10-31T19:47:21.832Z
Updated: 2025-04-16T17:43:36.141Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2022-41629 |
vulnerable | 2026-06-03 14:48:05.666680 |
Details available
HIGH (7.5)
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior allow unauthenticated users to access the aprunning endpoint, which could allow an attacker to retrieve any file from the “RunningConfigs” directory. The attacker could then view and modify configuration files such as UserListInfo.xml, which would allow them to see existing administrative passwords.
Published: 2022-10-31T19:51:27.025Z
Updated: 2025-04-16T16:06:21.139Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2022-40202 |
vulnerable | 2026-06-03 14:48:00.676269 |
Details available
CRITICAL (9.8)
The database backup function in Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior lacks proper authentication. An attacker could provide malicious serialized objects which, when deserialized, could activate an opcode for a backup scheduling function without authentication. This function allows the user to designate all function arguments and the file to be executed. This could allow the attacker to start any new process and achieve remote code execution.
Published: 2022-10-31T19:35:08.629Z
Updated: 2025-04-16T16:06:43.696Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2022-38142 |
vulnerable | 2026-06-03 14:47:49.341337 |
Details available
CRITICAL (9.8)
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize user-supplied data provided through the Device-Gateway service port without proper verification. An attacker could provide malicious serialized objects to execute arbitrary code upon deserialization.
Published: 2022-10-31T19:04:37.834Z
Updated: 2025-04-16T16:07:06.649Z Reference links |
Imported from gcve-enriched-dumps CVE data |
Contribute