Approved changes feed: RSS · Atom

cpe:2.3:a:deltaww:infrasuite_device_master:*:*:*:*:*:*:*:*

part: a version: * update: *

VendorDeltaww (ad3e3879-744a-547a-8a68-13ba5faaf0a4)
ProductInfrasuite Device Master (eedd7529-b297-5143-9e42-d1a5d10c0cf4)
Edition*
Language*
Software edition*
Target software*
Target hardware*
Other*
NotesImported from gcve-enriched-dumps CVE data

PURL mappings

PURLSourceLast updated
No PURL mappings for this CPE yet.

Vulnerability references

IdentifiercpeApplicabilitySubmitteddb.gcve.eu detailsRationale
CVE:CVE-2024-10456 vulnerable 2026-06-03 14:54:11.767526 Delta Electronics InfraSuite Device Master Deserialization of Untrusted Data
CRITICAL (9.8)
Delta Electronics InfraSuite Device Master versions prior to 1.0.12 are affected by a deserialization vulnerability that targets the Device-Gateway, which could allow deserialization of arbitrary .NET objects prior to authentication.
Published: 2024-10-30T18:04:52.786Z
Updated: 2024-10-30T18:15:45.431Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-34347 vulnerable 2026-06-03 14:52:16.270798 ​Delta Electronics InfraSuite Device Master Deserialization of Untrusted Data
CRITICAL (9.8)
​Delta Electronics InfraSuite Device Master versions prior to 1.0.7 contains classes that cannot be deserialized, which could allow an attack to remotely execute arbitrary code.
Published: 2023-07-10T18:59:30.158Z
Updated: 2024-11-08T17:43:56.320Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-34316 vulnerable 2026-06-03 14:52:16.228683 Delta Electronics InfraSuite Device Master Improper Access Control
MEDIUM (6.5)
​An attacker could bypass the latest Delta Electronics InfraSuite Device Master (versions prior to 1.0.7) patch, which could allow an attacker to retrieve file contents.
Published: 2023-07-10T19:01:51.280Z
Updated: 2025-01-27T16:20:03.560Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-30765 vulnerable 2026-06-03 14:51:53.697006 ​Delta Electronics InfraSuite Device Master Improper Access Control
HIGH (8.8)
​Delta Electronics InfraSuite Device Master versions prior to 1.0.7 contain improper access controls that could allow an attacker to alter privilege management configurations, resulting in privilege escalation.
Published: 2023-07-10T19:04:41.114Z
Updated: 2025-01-27T16:19:08.718Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-1145 vulnerable 2026-06-03 14:48:53.835784 Details available
HIGH (7.8)
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 are affected by a deserialization vulnerability targeting the Device-DataCollect service, which could allow deserialization of requests prior to authentication, resulting in remote code execution.
Published: 2023-03-27T14:56:30.287Z
Updated: 2025-01-16T21:39:05.219Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-1144 vulnerable 2026-06-03 14:48:53.835392 CVE-2023-1144
HIGH (8.8)
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contains an improper access control vulnerability in which an attacker can use the Device-Gateway service and bypass authorization, which could result in privilege escalation.
Published: 2023-03-27T14:43:11.987Z
Updated: 2025-01-16T21:40:57.021Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-1143 vulnerable 2026-06-03 14:48:53.835096 CVE-2023-1143
HIGH (8.8)
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an attacker could use Lua scripts, which could allow an attacker to remotely execute arbitrary code.
Published: 2023-03-27T14:46:20.000Z
Updated: 2025-01-16T21:39:49.421Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-1142 vulnerable 2026-06-03 14:48:53.834807 CVE-2023-1142
HIGH (7.5)
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an attacker could use URL decoding to retrieve system files, credentials, and bypass authentication resulting in privilege escalation.
Published: 2023-03-27T14:48:55.406Z
Updated: 2025-01-16T21:39:34.845Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-1141 vulnerable 2026-06-03 14:48:53.834529 CVE-2023-1141
HIGH (8.8)
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a command injection vulnerability that could allow an attacker to inject arbitrary commands, which could result in remote code execution.
Published: 2023-03-27T14:51:43.547Z
Updated: 2025-01-16T21:39:20.180Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-1140 vulnerable 2026-06-03 14:48:53.834238 CVE-2023-1140
CRITICAL (9.8)
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability that could allow an attacker to achieve unauthenticated remote code execution in the context of an administrator.
Published: 2023-03-27T14:54:53.192Z
Updated: 2025-01-16T21:39:13.175Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-1139 vulnerable 2026-06-03 14:48:53.833949 CVE-2023-1139
HIGH (8.8)
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 are affected by a deserialization vulnerability targeting the Device-gateway service, which could allow deserialization of requests prior to authentication, resulting in remote code execution.
Published: 2023-03-27T14:36:28.810Z
Updated: 2025-01-16T21:41:21.901Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-1138 vulnerable 2026-06-03 14:48:53.833648 CVE-2023-1138
HIGH (7.5)
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain an improper access control vulnerability, which could allow an attacker to retrieve Gateway configuration files to obtain plaintext credentials.
Published: 2023-03-27T14:41:48.610Z
Updated: 2025-01-16T21:41:09.760Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-1137 vulnerable 2026-06-03 14:48:53.833340 CVE-2023-1137
MEDIUM (6.5)
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability in which a low-level user could extract files and plaintext credentials of administrator users, resulting in privilege escalation.
Published: 2023-03-27T14:44:40.332Z
Updated: 2025-01-16T21:40:39.590Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-1136 vulnerable 2026-06-03 14:48:53.833027 CVE-2023-1136
CRITICAL (9.8)
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an unauthenticated attacker could generate a valid token, which would lead to authentication bypass.
Published: 2023-03-27T14:50:18.966Z
Updated: 2025-01-16T21:39:27.485Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-1135 vulnerable 2026-06-03 14:48:53.832716 Details available
HIGH (7.8)
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an attacker could set incorrect directory permissions, which could result in local privilege escalation.
Published: 2023-03-27T14:59:57.462Z
Updated: 2025-01-16T21:38:57.559Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-1134 vulnerable 2026-06-03 14:48:53.832284 CVE-2023-1134
HIGH (7.1)
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 are affected by a path traversal vulnerability, which could allow an attacker to read local files, disclose plaintext credentials, and escalate privileges.
Published: 2023-03-27T14:47:43.501Z
Updated: 2025-01-16T21:39:42.531Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2023-1133 vulnerable 2026-06-03 14:48:53.831854 CVE-2023-1133
CRITICAL (9.8)
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability in which the Device-status service listens on port 10100/ UDP by default. The service accepts the unverified UDP packets and deserializes the content, which could allow an unauthenticated attacker to remotely execute arbitrary code.
Published: 2023-03-27T14:33:18.921Z
Updated: 2025-02-13T16:39:15.943Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2022-41779 vulnerable 2026-06-03 14:48:05.979435 Details available
HIGH (8.8)
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize network packets without proper verification. If the device connects to an attacker-controlled server, the attacker could send maliciously crafted packets that would be deserialized and executed, leading to remote code execution.
Published: 2022-10-31T19:19:35.913Z
Updated: 2025-04-16T17:43:44.238Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2022-41778 vulnerable 2026-06-03 14:48:05.979046 Details available
CRITICAL (9.8)
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize user-supplied data provided through the Device-DataCollect service port without proper verification. An attacker could provide malicious serialized objects to execute arbitrary code upon deserialization.
Published: 2023-01-12T23:19:47.452Z
Updated: 2025-01-16T22:02:07.832Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2022-41776 vulnerable 2026-06-03 14:48:05.973949 Details available
HIGH (7.5)
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior allow unauthenticated users to trigger the WriteConfiguration method, which could allow an attacker to provide new values for user configuration files such as UserListInfo.xml. This could lead to the changing of administrative passwords.
Published: 2022-10-31T19:48:17.936Z
Updated: 2025-04-16T16:06:29.428Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2022-41772 vulnerable 2026-06-03 14:48:05.972849 Details available
CRITICAL (9.8)
Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior mishandle .ZIP archives containing characters used in path traversal. This path traversal could result in remote code execution.
Published: 2022-10-31T19:26:33.695Z
Updated: 2025-04-16T16:06:52.076Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2022-41688 vulnerable 2026-06-03 14:48:05.799656 Details available
CRITICAL (9.8)
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior lack proper authentication for functions that create and modify user groups. An attacker could provide malicious serialized objects that could run these functions without authentication to create a new user and add them to the administrator group.
Published: 2022-10-31T19:38:21.943Z
Updated: 2025-04-16T16:06:36.155Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2022-41657 vulnerable 2026-06-03 14:48:05.712766 Details available
CRITICAL (9.8)
Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior allow attacker provided data already serialized into memory to be used in file operation application programmable interfaces (APIs). This could create arbitrary files, which could be used in API operations and could ultimately result in remote code execution.
Published: 2022-10-31T19:24:37.976Z
Updated: 2025-04-16T16:06:59.095Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2022-41644 vulnerable 2026-06-03 14:48:05.690474 Details available
HIGH (8.8)
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior lacks authentication for a function that changes group privileges. An attacker could use this to create a denial-of-service state or escalate their own privileges.
Published: 2022-10-31T19:47:21.832Z
Updated: 2025-04-16T17:43:36.141Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2022-41629 vulnerable 2026-06-03 14:48:05.666680 Details available
HIGH (7.5)
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior allow unauthenticated users to access the aprunning endpoint, which could allow an attacker to retrieve any file from the “RunningConfigs” directory. The attacker could then view and modify configuration files such as UserListInfo.xml, which would allow them to see existing administrative passwords.
Published: 2022-10-31T19:51:27.025Z
Updated: 2025-04-16T16:06:21.139Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2022-40202 vulnerable 2026-06-03 14:48:00.676269 Details available
CRITICAL (9.8)
The database backup function in Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior lacks proper authentication. An attacker could provide malicious serialized objects which, when deserialized, could activate an opcode for a backup scheduling function without authentication. This function allows the user to designate all function arguments and the file to be executed. This could allow the attacker to start any new process and achieve remote code execution.
Published: 2022-10-31T19:35:08.629Z
Updated: 2025-04-16T16:06:43.696Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2022-38142 vulnerable 2026-06-03 14:47:49.341337 Details available
CRITICAL (9.8)
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize user-supplied data provided through the Device-Gateway service port without proper verification. An attacker could provide malicious serialized objects to execute arbitrary code upon deserialization.
Published: 2022-10-31T19:04:37.834Z
Updated: 2025-04-16T16:07:06.649Z
Reference links
Imported from gcve-enriched-dumps CVE data

Contribute

You can submit an edit proposal for this CPE entry or suggest a related product/vendor addition using the action button above.