Compactlogix 5370
Approved changes feed: RSS · Atom
cpe:2.3:a:rockwell_automation:compactlogix_5370:*:*:*:*:*:*:*:*
part: a version: * update: *
| Vendor | Rockwell Automation (dde15a4c-943a-57fe-888d-2bc03ade6545) |
|---|---|
| Product | Compactlogix 5370 (3a300b4e-4451-5f6b-8657-73406cbdfd35) |
| Edition | * |
| Language | * |
| Software edition | * |
| Target software | * |
| Target hardware | * |
| Other | * |
| Notes | Imported from gcve-enriched-dumps CVE data |
PURL mappings
| PURL | Source | Last updated |
|---|---|---|
| No PURL mappings for this CPE yet. | ||
Vulnerability references
| Identifier | cpeApplicability | Submitted | db.gcve.eu details | Rationale |
|---|---|---|---|---|
CVE:CVE-2026-9307 |
vulnerable | 2026-07-29 01:09:06.992037 |
Rockwell Automation CompactLogix 5370 Controllers – Multiple Vulnerabilities
A sensitive information disclosure security issue exists within the affected CompactLogix controllers. The controller's web server exposes CIP Connection IDs on the diagnostics webpage, which are accessible to any unauthenticated user on the network. This information can be leveraged by an attacker to construct malicious packets, leading to Denial-of-Service.
Published: 2026-06-16T13:42:08.999Z
Updated: 2026-06-16T17:49:40.834Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2025-11694 |
vulnerable | 2026-07-28 23:18:01.654993 |
Rockwell Automation CompactLogix 5370 Controllers – Multiple Vulnerabilities
A security issue exists within 1769 CompactLogix controllers due to the missing validation of sequence numbers and source IP addresses in the CIP protocol. This allows attacker to abuse the exposed Connection ID’s visible on the web interface to perform denial-of-service attacks, resulting in a minor fault.
Published: 2026-06-16T13:39:46.158Z
Updated: 2026-06-16T17:48:53.691Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2022-3157 |
vulnerable | 2026-06-08 05:47:19.575270 |
Rockwell Automation GuardLogix and ControlLogix controllers Vulnerable to Denial-Of-Service Attack
HIGH (8.6)
A vulnerability exists in the Rockwell Automation controllers that allows a malformed CIP request to cause a major non-recoverable fault (MNRF) and a denial-of-service condition (DOS).
Published: 2022-12-16T20:35:55.689Z
Updated: 2025-04-16T14:32:17.798Z |
Imported from gcve-enriched-dumps CVE data |
Contribute