Simatic S7 1500 Cpu 1513Pro F 2 Pn
Approved changes feed: RSS · Atom
cpe:2.3:a:siemens:simatic_s7-1500_cpu_1513pro_f-2_pn:*:*:*:*:*:*:*:*
part: a version: * update: *
| Vendor | Siemens (4bd2a91b-02ad-5c3d-b25f-70697e0c9d7f) |
|---|---|
| Product | Simatic S7 1500 Cpu 1513Pro F 2 Pn (d0a008be-5954-52d6-b3c6-7d5400f43ef8) |
| Edition | * |
| Language | * |
| Software edition | * |
| Target software | * |
| Target hardware | * |
| Other | * |
| Notes | Imported from gcve-enriched-dumps CVE data |
PURL mappings
| PURL | Source | Last updated |
|---|---|---|
| No PURL mappings for this CPE yet. | ||
Vulnerability references
| Identifier | cpeApplicability | Submitted | db.gcve.eu details | Rationale |
|---|---|---|---|---|
CVE:CVE-2026-25789 |
vulnerable | 2026-06-08 07:53:20.461025 |
Details available
HIGH (7.1)
Affected devices do not properly validate and sanitize filenames on the Firmware Update page. This could allow a remote attacker to social engineer the user into selecting the modified firmware file to be uploaded. This would result in malitcious JavaScript execution in the context of the authenticated user's session without requiring the file to be uploaded, potentially leading to session hijacking or credential theft.
Published: 2026-05-12T08:21:10.076Z
Updated: 2026-07-14T09:19:16.119Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2026-25787 |
vulnerable | 2026-06-08 07:53:20.452736 |
Details available
CRITICAL (9.1)
Affected devices do not properly validate and sanitize Technology Object (TO) name rendered on the "Motion Control Diagnostics" page of the web interface. This could allow an authenticated attacker who is authorized to download a TIA project into the product, to inject malicious scripts into the page.
If a benign user with appropriate rights accesses the "Motion Control Diagnostics" parameters page, the malicious code would be executed in the scope of their web session.
Published: 2026-05-12T08:21:06.426Z
Updated: 2026-07-14T09:19:14.087Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2026-25786 |
vulnerable | 2026-06-08 07:53:20.375340 |
Details available
CRITICAL (9.1)
Affected devices do not properly validate and sanitize PLC/station name rendered on the "communication" parameters page of the web interface.
This could allow an authenticated attacker who is authorized to download a TIA project into the product, to inject malicious scripts into the page.
If a benign user with appropriate rights accesses the "communication" parameters page, the malicious code would be executed in the scope of their web session.
Published: 2026-05-12T08:20:58.605Z
Updated: 2026-07-14T09:19:12.039Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2025-40943 |
vulnerable | 2026-06-08 07:25:06.371420 |
Details available
CRITICAL (9.6)
Affected devices do not properly sanitize contents of trace files.
This could allow an attacker to inject code through social engineering an authorized user, who has the function right "Read diagnostics", to import a specially crafted trace file.
The malicious trace file is insufficiently sanitized and malicious code could be executed in the clients browser session and trigger PLC operations via the webserver that the legitimate user is authorized to perform.
Published: 2026-03-10T16:07:50.385Z
Updated: 2026-05-12T08:20:49.293Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2024-46887 |
vulnerable | 2026-06-08 06:48:10.768798 |
Details available
MEDIUM (5.3)
The web server of affected devices do not properly authenticate user request to the '/ClientArea/RuntimeInfoData.mwsl' endpoint. This could allow an unauthenticated remote attacker to gain knowledge about current actual and configured maximum cycle times as well as about configured maximum communication load.
Published: 2024-10-08T08:40:43.510Z
Updated: 2025-10-21T14:12:27.657Z Reference links |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2024-46886 |
vulnerable | 2026-06-08 06:48:10.695200 | db.gcve.eu details were skipped to keep the page responsive. | Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2023-37482 |
vulnerable | 2026-06-08 06:08:15.447951 | db.gcve.eu details were skipped to keep the page responsive. | Imported from gcve-enriched-dumps CVE data |
Contribute
You can submit an edit proposal for this CPE entry or suggest a related product/vendor addition using the action button above.