Iot Interface & Cmc Iii Processing Unit
Approved changes feed: RSS · Atom
cpe:2.3:a:rittal_gmbh_&_co._kg:iot_interface_&_cmc_iii_processing_unit:*:*:*:*:*:*:*:*part: a version: * update: *
| Vendor | Rittal Gmbh & Co. Kg (258383c0-cbe7-5328-8ab3-f2c969e05352) |
|---|---|
| Product | Iot Interface & Cmc Iii Processing Unit (f8dbe36c-dbc1-5c51-820c-5d645ff64859) |
| Edition | * |
| Language | * |
| Software edition | * |
| Target software | * |
| Target hardware | * |
| Other | * |
Notes
Imported from gcve-enriched-dumps CVE data
PURL mappings
| PURL | Source | Last updated |
|---|---|---|
| No PURL mappings for this CPE yet. | ||
Vulnerability references
| Identifier | cpeApplicability | Submitted | db.gcve.eu details | Rationale |
|---|---|---|---|---|
CVE:CVE-2024-47945 |
vulnerable | 2026-06-08 06:48:13.462026 |
Predictable Session ID
The devices are vulnerable to session hijacking due to insufficient
entropy in its session ID generation algorithm. The session IDs are
predictable, with only 32,768 possible values per user, which allows
attackers to pre-generate valid session IDs, leading to unauthorized
access to user sessions. This is not only due to the use of an
(insecure) rand() function call but also because of missing
initialization via srand(). As a result only the PIDs are effectively
used as seed.
Published: 2024-10-15T10:05:58.333Z
Updated: 2025-11-03T22:21:56.044Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2024-47944 |
vulnerable | 2026-06-08 06:48:13.461501 |
Missing Protection Mechanism for Alternate Hardware Interface
The device directly executes .patch firmware upgrade files on a USB stick without any prior authentication in the admin interface. This leads to an unauthenticated code execution via the firmware upgrade function.
Published: 2024-10-15T09:00:30.605Z
Updated: 2025-11-03T22:21:54.572Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2024-47943 |
vulnerable | 2026-06-08 06:48:13.460429 |
Improper signature verification of firmware upgrade files
The firmware upgrade function in the admin web interface of the Rittal IoT Interface & CMC III Processing Unit devices checks if
the patch files are signed before executing the containing run.sh
script. The signing process is kind of an HMAC with a long string as key
which is hard-coded in the firmware and is freely available for
download. This allows crafting malicious "signed" .patch files in order
to compromise the device and execute arbitrary code.
Published: 2024-10-15T08:57:05.068Z
Updated: 2025-11-03T22:21:53.100Z |
Imported from gcve-enriched-dumps CVE data |