Approved changes feed: RSS · Atom

cpe:2.3:h:endress:meac300-fnade4:-:*:*:*:*:*:*:*

part: h version: - update: *

VendorEndress (3c08e0d0-0a0b-59fa-8b29-bcefa13da872)
ProductMeac300 Fnade4 (5b5a96ee-1f35-5448-9deb-1cb1080526ae)
Edition*
Language*
Software edition*
Target software*
Target hardware*
Other*
NotesImported from gcve-enriched-dumps CVE data

PURL mappings

PURLSourceLast updated
No PURL mappings for this CPE yet.

Vulnerability references

IdentifiercpeApplicabilitySubmitteddb.gcve.eu detailsRationale
CVE:CVE-2025-27461 not_vulnerable 2026-06-03 15:00:12.520051 CVE-2025-27461
HIGH (7.6)
During startup, the device automatically logs in the EPC2 Windows user without requesting a password.
Published: 2025-07-03T11:34:52.786Z
Updated: 2025-07-03T13:15:27.472Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-27460 not_vulnerable 2026-06-03 15:00:12.519494 CVE-2025-27460
HIGH (7.6)
The hard drives of the device are not encrypted using a full volume encryption feature such as BitLocker. This allows an attacker with physical access to the device to use an alternative operating system to interact with the hard drives, completely circumventing the Windows login. The attacker can read from and write to all files on the hard drives.
Published: 2025-07-03T11:34:21.220Z
Updated: 2025-07-03T13:15:32.379Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-27459 not_vulnerable 2026-06-03 15:00:12.519044 CVE-2025-27459
MEDIUM (4.4)
The VNC application stores its passwords encrypted within the registry but uses DES for encryption. As DES is broken, the original passwords can be recovered.
Published: 2025-07-03T11:33:53.899Z
Updated: 2025-07-03T13:15:37.506Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-27458 not_vulnerable 2026-06-03 15:00:12.518460 CVE-2025-27458
MEDIUM (6.5)
The VNC authentication mechanism bases on a challenge-response system where both server and client use the same password for encryption. The challenge is sent from the server to the client, is encrypted by the client and sent back. The server does the same encryption locally and if the responses match it is prooven that the client knows the correct password. Since all VNC communication is unencrypted, an attacker can obtain the challenge and response and try to derive the password from this information.
Published: 2025-07-03T11:33:30.605Z
Updated: 2025-07-03T13:15:43.013Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-27457 not_vulnerable 2026-06-03 15:00:12.517813 CVE-2025-27457
MEDIUM (6.5)
All communication between the VNC server and client(s) is unencrypted. This allows an attacker to intercept the traffic and obtain sensitive data.
Published: 2025-07-03T11:32:59.576Z
Updated: 2025-07-03T13:15:48.078Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-27456 not_vulnerable 2026-06-03 15:00:12.506005 CVE-2025-27456
HIGH (7.5)
The SMB server's login mechanism does not implement sufficient measures to prevent multiple failed authentication attempts within a short time frame, making it susceptible to brute-force attacks.
Published: 2025-07-03T11:32:21.466Z
Updated: 2025-07-03T13:15:53.469Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-27455 not_vulnerable 2026-06-03 15:00:12.505530 CVE-2025-27455
MEDIUM (4.3)
The web application is vulnerable to clickjacking attacks. The site can be embedded into another frame, allowing an attacker to trick a user into clicking on something different from what the user perceives, thus potentially revealing confidential information or allowing others to take control of their computer while clicking on seemingly innocuous objects.
Published: 2025-07-03T11:30:49.265Z
Updated: 2025-07-03T13:15:59.115Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-27454 not_vulnerable 2026-06-03 15:00:12.505047 CVE-2025-27454
MEDIUM (4.3)
The application is vulnerable to cross-site request forgery. An attacker can trick a valid, logged in user into submitting a web request that they did not intend. The request uses the victim's browser's saved authorization to execute the request.
Published: 2025-07-03T11:30:19.944Z
Updated: 2025-07-03T13:16:05.545Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-27453 not_vulnerable 2026-06-03 15:00:12.504551 CVE-2025-27453
MEDIUM (5.3)
The HttpOnly flag is set to false on the PHPSESSION cookie. Therefore, the cookie can be accessed by other sources such as JavaScript.
Published: 2025-07-03T11:29:48.216Z
Updated: 2025-07-03T13:16:11.391Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-27452 not_vulnerable 2026-06-03 15:00:12.503940 CVE-2025-27452
MEDIUM (5.3)
The configuration of the Apache httpd webserver which serves the MEAC300-FNADE4 web application, is partly insecure. There are modules activated that are not required for the operation of the FNADE4 web application. The functionality of the some modules pose a risk to the webserver which enable dircetory listing.
Published: 2025-07-03T11:29:04.003Z
Updated: 2025-07-03T13:16:16.586Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-27451 not_vulnerable 2026-06-03 15:00:12.503451 CVE-2025-27451
MEDIUM (5.3)
For failed login attempts, the application returns different error messages depending on whether the login failed due to an incorrect password or a non-existing username. This allows an attacker to guess usernames until they find an existing one.
Published: 2025-07-03T11:27:35.372Z
Updated: 2025-07-03T13:16:21.696Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-27450 not_vulnerable 2026-06-03 15:00:12.502849 CVE-2025-27450
MEDIUM (6.5)
The Secure attribute is missing on multiple cookies provided by the MEAC300-FNADE4. An attacker can trick a user to establish an unencrypted HTTP connection to the server and intercept the request containing the PHPSESSID cookie.
Published: 2025-07-03T11:26:33.462Z
Updated: 2025-07-03T13:16:27.030Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-27449 not_vulnerable 2026-06-03 15:00:12.502363 CVE-2025-27449
HIGH (7.5)
The MEAC300-FNADE4 does not implement sufficient measures to prevent multiple failed authentication attempts within a short time frame, making it susceptible to brute-force attacks.
Published: 2025-07-03T11:25:45.104Z
Updated: 2025-07-03T13:16:31.757Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-27448 not_vulnerable 2026-06-03 15:00:12.501818 CVE-2025-27448
MEDIUM (6.8)
The web application is susceptible to cross-site-scripting attacks. An attacker who can create new dashboards can inject JavaScript code into the dashboard name which will be executed when the website is loaded.
Published: 2025-07-03T11:24:00.307Z
Updated: 2025-07-03T13:16:36.782Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-27447 not_vulnerable 2026-06-03 15:00:12.501076 CVE-2025-27447
HIGH (7.4)
The web application is susceptible to cross-site-scripting attacks. An attacker can create a prepared URL, which injects JavaScript code into the website. The code is executed in the victim’s browser when an authenticated administrator clicks the link.
Published: 2025-07-03T11:23:20.043Z
Updated: 2025-07-03T13:16:41.793Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-1711 not_vulnerable 2026-06-03 14:59:06.207615 CVE-2025-1711
MEDIUM (4.3)
Multiple services of the DUT as well as different scopes of the same service reuse the same credentials.
Published: 2025-07-03T11:22:09.710Z
Updated: 2025-07-03T13:16:47.136Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-1710 not_vulnerable 2026-06-03 14:59:06.207034 CVE-2025-1710
HIGH (7.5)
The maxView Storage Manager does not implement sufficient measures to prevent multiple failed authentication attempts within a short time frame, making it susceptible to brute-force attacks.
Published: 2025-07-03T11:21:18.058Z
Updated: 2025-07-03T13:16:53.110Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-1709 not_vulnerable 2026-06-03 14:59:06.206401 CVE-2025-1709
MEDIUM (6.5)
Several credentials for the local PostgreSQL database are stored in plain text (partially base64 encoded).
Published: 2025-07-03T11:20:20.793Z
Updated: 2025-07-03T13:17:00.475Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-1708 not_vulnerable 2026-06-03 14:59:06.205912 CVE-2025-1708
HIGH (8.6)
The application is vulnerable to SQL injection attacks. An attacker is able to dump the PostgreSQL database and read its content.
Published: 2025-07-03T11:18:22.134Z
Updated: 2025-07-03T13:17:20.348Z
Reference links
Imported from gcve-enriched-dumps CVE data

Contribute

You can submit an edit proposal for this CPE entry or suggest a related product/vendor addition using the action button above.