cpe:2.3:a:honeywell:c200e:*:*:*:*:*:*:*:*

part: a version: * update: *

VendorHoneywell (98681534-528d-57d2-bf2a-17f1d63c09c9)
ProductC200E (03c04c45-57d4-5b57-910b-1c4cc82f9bde)
Edition*
Language*
Software edition*
Target software*
Target hardware*
Other*
NotesImported from gcve-enriched-dumps CVE data

PURL mappings

PURLSourceLast updated
No PURL mappings for this CPE yet.

Vulnerability references

IdentifiercpeApplicabilitySubmitteddb.gcve.eu detailsRationale
CVE:CVE-2025-3947 vulnerable 2026-06-08 07:23:10.210363 Integer underflow during processing of short network packets in CDA FTEB responder
HIGH (8.2)
The Honeywell Experion PKS contains an Integer Underflow vulnerability in the component Control Data Access (CDA). An attacker could potentially exploit this vulnerability, leading to Input Data Manipulation, which could result in improper integer data value checking during subtraction leading to a denial of service. Honeywell recommends updating to the most recent version of Honeywell Experion PKS:520.2 TCU9 HF1 and 530.1 TCU3 HF1. The affected Experion PKS products are C300 PCNT02, C300 PCNT05, FIM4, FIM8, UOC, CN100, HCA, C300PM, and C200E. The Experion PKS versions affected are from 520.1 through 520.2 TCU9 and from 530 through 530 TCU3.
Published: 2025-07-10T20:19:13.991Z
Updated: 2025-08-04T19:46:31.982Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-3946 vulnerable 2026-06-08 07:23:10.207817 Incorrect response generation during FTEB protocol processing
HIGH (8.2)
The Honeywell Experion PKS and OneWireless WDM contains a Deployment of Wrong Handler vulnerability in the component Control Data Access (CDA). An attacker could potentially exploit this vulnerability, leading to Input Data Manipulation, which could result in incorrect handling of packets leading to remote code execution. Honeywell recommends updating to the most recent version of Honeywell Experion PKS:520.2 TCU9 HF1 and 530.1 TCU3 HF1 and OneWireless: 322.5 and 331.1. The affected Experion PKS products are C300 PCNT02, C300 PCNT05, FIM4, FIM8, UOC, CN100, HCA, C300PM, and C200E. The Experion PKS versions affected are from 520.1 through 520.2 TCU9 and from 530 through 530 TCU3. The OneWireless WDM affected versions are 322.1 through 322.4 and 330.1 through 330.3.
Published: 2025-07-10T20:16:54.743Z
Updated: 2025-08-04T19:46:15.112Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-2523 vulnerable 2026-06-08 07:16:57.300844 Lack of buffer clearing before reuse may result in incorrect system behavior.
CRITICAL (9.4)
The Honeywell Experion PKS and OneWireless WDM contains an Integer Underflow vulnerability in the component Control Data Access (CDA). An attacker could potentially exploit this vulnerability, leading to a Communication Channel Manipulation, which could result in a failure during subtraction allowing remote code execution. Honeywell recommends updating to the most recent version of Honeywell Experion PKS:520.2 TCU9 HF1 and 530.1 TCU3 HF1 and OneWireless: 322.5 and 331.1. The affected Experion PKS products are C300 PCNT02, C300 PCNT05, FIM4, FIM8, UOC, CN100, HCA, C300PM, and C200E. The Experion PKS versions affected are from 520.1 through 520.2 TCU9 and from 530 through 530 TCU3. The OneWireless WDM affected versions are 322.1 through 322.4 and 330.1 through 330.3.
Published: 2025-07-10T20:15:32.600Z
Updated: 2025-08-04T19:45:51.105Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-2522 vulnerable 2026-06-08 07:16:57.296591 Lack of buffer clearing before reuse may result in incorrect system behavior.
MEDIUM (6.5)
The Honeywell Experion PKS and OneWireless WDM contains Sensitive Information in Resource vulnerability in the component Control Data Access (CDA). An attacker could potentially exploit this vulnerability, leading to a Communication Channel Manipulation, which could result in buffer reuse which may cause incorrect system behavior. Honeywell also recommends updating to the most recent version of Honeywell Experion PKS:520.2 TCU9 HF1 and 530.1 TCU3 HF1 and OneWireless: 322.5 and 331.1.  The affected Experion PKS products are C300, FIM4, FIM8, UOC, CN100, HCA, C300PM, and C200E. The Experion PKS versions affected are 520.1 before 520.2 TCU9 HF1 and 530 before 530 TCU3. The OneWireless WDM affected versions are 322.1 through 322.4 and 330.1 through 330.3.
Published: 2025-07-10T20:11:43.603Z
Updated: 2025-08-04T19:45:13.439Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2025-2521 vulnerable 2026-06-08 07:16:57.293724 Lack of indexes’ validation against buffer borders leads to remote code execution.
HIGH (8.6)
The Honeywell Experion PKS and OneWireless WDM contains a Memory Buffer vulnerability in the component Control Data Access (CDA). An attacker could potentially exploit this vulnerability, leading to an Overread Buffers, which could result in improper index validation against buffer borders leading to remote code execution. Honeywell recommends updating to the most recent version of Honeywell Experion PKS: 520.2 TCU9 HF1 and 530.1 TCU3 HF1 and OneWireless: 322.5 and 331.1. The affected Experion PKS products are C300 PCNT02, C300 PCNT05, FIM4, FIM8, UOC, CN100, HCA, C300PM, and C200E. The Experion PKS versions affected are from 520.1 through 520.2 TCU9 and from 530 through 530 TCU3.The OneWireless WDM affected versions are 322.1 through 322.4 and 330.1 through 330.3.
Published: 2025-07-10T20:08:04.077Z
Updated: 2025-08-04T19:44:27.744Z
Reference links
Imported from gcve-enriched-dumps CVE data

Contribute