Approved changes feed: RSS · Atom
cpe:2.3:a:honeywell:iq412:*:*:*:*:*:*:*:*
part: a version: * update: *
| Vendor | Honeywell (98681534-528d-57d2-bf2a-17f1d63c09c9) |
|---|---|
| Product | Iq412 (bcf5f29d-c02a-5a34-a626-5e14a54d6810) |
| Edition | * |
| Language | * |
| Software edition | * |
| Target software | * |
| Target hardware | * |
| Other | * |
| Notes | Imported from gcve-enriched-dumps CVE data |
PURL mappings
| PURL | Source | Last updated |
|---|---|---|
| No PURL mappings for this CPE yet. | ||
Vulnerability references
| Identifier | cpeApplicability | Submitted | db.gcve.eu details | Rationale |
|---|---|---|---|---|
CVE:CVE-2026-3611 |
vulnerable | 2026-06-08 08:01:19.067860 |
Honeywell IQ4x BMS Controller Missing authentication for critical function
CRITICAL (10)
The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
Published: 2026-03-12T20:06:05.753Z
Updated: 2026-03-30T15:26:08.604Z |
Imported from gcve-enriched-dumps CVE data |
Contribute
You can submit an edit proposal for this CPE entry or suggest a related product/vendor addition using the action button above.