Approved changes feed: RSS · Atom

cpe:2.3:a:honeywell:iq41x:*:*:*:*:*:*:*:*

part: a version: * update: *

VendorHoneywell (98681534-528d-57d2-bf2a-17f1d63c09c9)
ProductIq41X (319342ee-cd1b-5370-a871-1e7264680bbe)
Edition*
Language*
Software edition*
Target software*
Target hardware*
Other*
NotesImported from gcve-enriched-dumps CVE data

PURL mappings

PURLSourceLast updated
No PURL mappings for this CPE yet.

Vulnerability references

IdentifiercpeApplicabilitySubmitteddb.gcve.eu detailsRationale
CVE:CVE-2026-3611 vulnerable 2026-06-08 08:01:19.070172 Honeywell IQ4x BMS Controller Missing authentication for critical function
CRITICAL (10)
The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
Published: 2026-03-12T20:06:05.753Z
Updated: 2026-03-30T15:26:08.604Z
Reference links
Imported from gcve-enriched-dumps CVE data