CVE:CVE-2021-25677 |
not_vulnerable | 2026-06-08 05:30:41.489764 |
Details available
MEDIUM (5.3)
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), SIMOTICS CONNECT 400 (All versions >= V0.5.0.0 < V1.0.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS client does not properly randomize DNS transaction IDs. That could allow an attacker to poison the DNS cache or spoof DNS resolving.
Published: 2021-04-22T20:42:21.000Z
Updated: 2024-08-03T20:11:28.339Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2020-27738 |
not_vulnerable | 2026-06-08 05:23:53.089593 |
Details available
MEDIUM (6.5)
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS domain name record decompression functionality does not properly validate the pointer offset values. The parsing of malformed responses could result in a read access past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition.
Published: 2021-04-22T20:42:20.000Z
Updated: 2024-08-04T16:18:45.774Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2020-27737 |
not_vulnerable | 2026-06-08 05:23:53.088421 |
Details available
MEDIUM (6.5)
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS response parsing functionality does not properly validate various length and counts of the records. The parsing of malformed responses could result in a read past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition or leak the memory past the allocated structure.
Published: 2021-04-22T20:42:19.000Z
Updated: 2024-08-04T16:18:45.586Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2020-27736 |
not_vulnerable | 2026-06-08 05:23:53.087248 |
Details available
MEDIUM (6.5)
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS domain name label parsing functionality does not properly validate the null-terminated name in DNS-responses. The parsing of malformed responses could result in a read past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition or leak the read memory.
Published: 2021-04-22T20:42:19.000Z
Updated: 2024-08-04T16:18:45.573Z |
Imported from gcve-enriched-dumps CVE data |
CVE:CVE-2019-13939 |
not_vulnerable | 2026-06-08 05:12:52.570480 |
Details available
HIGH (7.1)
A vulnerability has been identified in APOGEE MEC/MBC/PXC (P2) (All versions < V2.8.2), APOGEE PXC Compact (BACnet) (All versions < V3.5.3), APOGEE PXC Compact (P2 Ethernet) (All versions >= V2.8.2 < V2.8.19), APOGEE PXC Modular (BACnet) (All versions < V3.5.3), APOGEE PXC Modular (P2 Ethernet) (All versions >= V2.8.2 < V2.8.19), Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303), Desigo PXC00-E.D (All versions >= V2.3 < V6.0.327), Desigo PXC00-U (All versions >= V2.3x and < V6.00.327), Desigo PXC001-E.D (All versions >= V2.3 < V6.0.327), Desigo PXC100-E.D (All versions >= V2.3 < V6.0.327), Desigo PXC12-E.D (All versions >= V2.3 < V6.0.327), Desigo PXC128-U (All versions >= V2.3x and < V6.00.327), Desigo PXC200-E.D (All versions >= V2.3 < V6.0.327), Desigo PXC22-E.D (All versions >= V2.3 < V6.0.327), Desigo PXC22.1-E.D (All versions >= V2.3 < V6.0.327), Desigo PXC36.1-E.D (All versions >= V2.3 < V6.0.327), Desigo PXC50-E.D (All versions >= V2.3 < V6.0.327), Desigo PXC64-U (All versions >= V2.3x and < V6.00.327), Desigo PXM20-E (All versions >= V2.3 < V6.0.327), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus Source Code (All versions), SIMOTICS CONNECT 400 (All versions < V0.3.0.330), TALON TC Compact (BACnet) (All versions < V3.5.3), TALON TC Modular (BACnet) (All versions < V3.5.3). By sending specially crafted DHCP packets to a device where the DHCP client is enabled, an attacker could change the IP address of the device to an invalid value.
Published: 2020-01-16T15:35:24.000Z
Updated: 2025-06-10T15:17:09.328Z Reference links
|