Approved changes feed: RSS · Atom

cpe:2.3:h:rockwellautomation:guardlogix_5570:-:*:*:*:*:*:*:*

part: h version: - update: *

VendorRockwellautomation (483fb14e-bfe0-5dc5-b460-aca202063cba)
ProductGuardlogix 5570 (a7349fa8-253c-5d97-9153-e2d1a57b04ed)
Edition*
Language*
Software edition*
Target software*
Target hardware*
Other*
NotesImported from NVD CPE 2.0 feed

PURL mappings

PURLSourceLast updated
No PURL mappings for this CPE yet.

Vulnerability references

IdentifiercpeApplicabilitySubmitteddb.gcve.eu detailsRationale
CVE:CVE-2022-3157 not_vulnerable 2026-06-08 05:47:19.589137 Rockwell Automation GuardLogix and ControlLogix controllers Vulnerable to Denial-Of-Service Attack
HIGH (8.6)
A vulnerability exists in the Rockwell Automation controllers that allows a malformed CIP request to cause a major non-recoverable fault (MNRF) and a denial-of-service condition (DOS).
Published: 2022-12-16T20:35:55.689Z
Updated: 2025-04-16T14:32:17.798Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2022-1797 not_vulnerable 2026-06-08 05:39:13.942062 Rockwell Automation Logix Controllers Uncontrolled Resource Consumption
MEDIUM (6.8)
A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online.
Published: 2022-05-31T19:04:44.000Z
Updated: 2025-04-16T16:17:49.601Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2022-1161 not_vulnerable 2026-06-08 05:39:12.332749 ICSA-22-090-05 Rockwell Automation Logix Controllers
CRITICAL (10)
An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other.
Published: 2022-04-11T19:38:14.725Z
Updated: 2025-04-16T16:31:12.359Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2021-22681 not_vulnerable 2026-06-08 05:30:01.069169 Details available
Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800.
Published: 2021-03-03T17:59:43.000Z
Updated: 2026-03-06T05:01:20.925Z
Reference links
Imported from gcve-enriched-dumps CVE data
CVE:CVE-2020-6998 not_vulnerable 2026-06-08 05:27:11.671983 Rockwell Automation CompactLogix 5370 and ControlLogix 5570 Controllers Improper Input Validation
MEDIUM (5.8)
The connection establishment algorithm found in Rockwell Automation CompactLogix 5370 and ControlLogix 5570 versions 33 and prior does not sufficiently manage its control flow during execution, creating an infinite loop. This may allow an attacker to send specially crafted CIP packet requests to a controller, which may cause denial-of-service conditions in communications with other products.
Published: 2022-07-27T20:18:00.000Z
Updated: 2025-04-17T15:51:02.651Z
Reference links
Imported from gcve-enriched-dumps CVE data

Contribute

You can submit an edit proposal for this CPE entry or suggest a related product/vendor addition using the action button above.